20 Troubleshooting
SMA America, LLC
204
SI4548_6048-US-TB_en-13
Technical description
19.6 Direct Access to the Parameters
19.6.1 Direct Access (600#)
Observe the information for the direct accessing of the parameters (see Section 10.3 "Direct Access
- Direct Access to the Parameters", page 82).
20 Troubleshooting
In general the Sunny Island distinguishes between events and errors.
•
Events
describe state changes or transient states (e.g. generator connection).
•
Errors
describe states that are not permitted or are only permitted up to a certain rate.
This includes warnings, failures and errors. User interaction is generally required.
20.1 Error Confirmation
If a disturbance or error occurs, the Sunny Island goes into standby.
Proceed as follows to confirm an error:
1. Remove the cause.
2. Confirm error with <ENTER>.
3. Start the Sunny Island again.
20.2 Autostart Handling
The Sunny Island has an autostart meter which counts down by 1 with every automatic start. If the
Sunny Island runs uninterrupted for over ten minutes, the autostart meter is reset to its initial value.
If another fault occurs when the autostart meter is at 0, the Sunny Island waits for ten minutes and then
attempts to restart. The autostart meter begins to run again.
The number of the autostarts allowed can be set using the "250.01 AutoStr" parameter (in standby
mode).