19.1.3 External Meters (130#)
#131 Total Meters
132# Grid State
#133 Generator State
No. Name
Description
01
TotExtPwrAt
Total active power of the external source in kW
02
TotExtCur
Total current of the external source in A
03
TotExtPwrRt
Total reactive power in kVAr
04
TotLodPwr
Total averaged active power of the consumers (cluster) in kW
05
TotMccLodPwr
Total averaged active power of the consumers (Multicluster) in kW
No. Name
Description
01
GdRmgTm
Remaining time of GdValTm parameter in hours, minutes and seconds
No. Name
Description
Display value
Plain text (No.)
Explanation
01
GnDmdSrc
Source for
generator request:
None (1)
No request
Bat (2)
Battery charge state-dependent
Lod (3)
Load-dependent
Tim (4)
Time-controlled
Run1h (5)
Requested for 1 hour
Start (6)
Manually started
ExtSrcReq (7)
Requested via an external
source
02
GnStt
Generator state
Off (1)
Off
Init (2)
Init
Ready (3)
Waiting for request (ready)
Warm (4)
Warming up
Connect (5)
Connecting
Run (6)
In operation
Retry (7)
Restarting
AC Disconnect (8) Disconnecting
Cool (9)
Cooling down
Lock (10)
Locked after gen operation
Fail (11)
Generator failure or error
FailLock (12)
Locked after gen failure