Parameter lists
SMA America, LLC
162
SI5048U-TUS121440
Technical Description
#223 Battery Protection
#224 Battery Silent Mode
No. Name
Description
Display value
Default value
01
BatPro1TmStr
Starting time of the
battery-
preservation mode
(level 1)
22:00:00
02
BatPro1TmStp
End time of battery-
preservation mode
(level 1)
06:00:00
03
BatPro2TmStr
Starting time of the
battery-
preservation mode
(level 2)
17:00:00
04
BatPro2TmStp
End time of battery-
preservation mode
(level 2)
09:00:00
05
BatPro1Soc
Battery charge
state for battery-
preservation mode
level 1
0 % … 70 %
20 %
06
BatPro2Soc
Battery charge
state for battery-
preservation mode
level 2
0 % … 70 %
15 %
07
BatPro3Soc
Battery charge
state for battery-
preservation mode
level 3
0 % … 70 %
10 %
No. Name
Description
Value
Explanation
Default
value
01
SilentEna
Silent mode on the
grid
Disable
disable
Disable
Enable
enable
02
SilentTmFlo
Maximum time for
float charge until
transfer into silent
1 h … 48 h
3 h
03
SilentTmMax
Maximum time for
silent until transfer
into float charge
1 h … 168 h
12 h