SMA America, LLC
Parameter lists
Technical Description
SI5048U-TUS121440
167
235# Generator Start
20
GnAlSns
AI sensitivity
Low
Low
Normal
Medium
Medium
Normal
Normal
High
High
No. Name
Description
Value
Explanation Default
value
01
GnAutoEna
Generator autostart
Off
Disable
On
On
Enable
02
GnAutoStr
Number of autostarts
3
03
GnSocTm1Str
SOC limit for switching on
generator for time 1
40 %
04
GnSocTm1Stp
SOC limit for switching off
generator for time 1
80 %
05
GnSocTm2Str
SOC limit for switching on
generator for time 2
40 %
06
GnSocTm2Stp
SOC limit for switching off
generator for time 2
80 %
07
GnTm1Str
Time 1 for generator request in
hours, minutes and seconds.
Begin: Time 1,
End: Time 2
08
GnTm2Str
Time 2 for generator request in
hours, minutes and seconds.
Begin: Time 2,
End: Time 1
09
GnPwrEna
Generator request based on
power
Off
Disable
Off
On
Enable
10
GnPwrStr
Generator request switch-on
power limit
4 kW
11
GnPwrStp
Generator request switch-off
power limit
2 kW
12
GnPwrAvgTm
Average time for power-
related generator start
60 sec
13
GnTmOpEna
Time-controlled generator
operation
Disable
Disable
Disable
Enable
Enable
No. Name
Description
Value
Explanation
Default
value