SMA America, LLC
Assembly
Technical Description
SI5048U-TUS121440
31
Observe the following conditions during mounting:
• The mounting method and mounting location must be suitable for the weight and dimensions of
the Sunny Island.
• Mount on a solid surface.
• The installation location must be accessible at all times.
• The ambient temperature must be between -13 °F (–25 °C) and 122 °F (+50 °C).
• Do not expose the Sunny Island to direct sunlight to avoid power reduction (derating) due to
excessive heating.
• Install the Sunny Island that way, that the display is at eye level in order to allow the operating
status to be read at all times.
• Install vertically or tilted backwards by 45° max.
• Never install the device with a forward tilt.
• Do not mount in a horizontal position.
• The connection area may not point upwards.
• The room air can have a humidity of up to 100%, but this must not be condensing.
• In a living area, do not mount the unit on
plasterboard walls etc. in order to avoid audible
vibrations.
The Sunny Island can make noises when in use
which can be considered a nuisance when installed
in a living area.