Generator interface #242.07 GnSrtMod GenMan; start at the
generator
14.1.4 Automatic Generator Operation
In automatic operating mode ("#241.01 GnAutoEna" parameter), the Sunny Island
5048 automatically defines the settings (depending on battery charge state or load) as
to when the generator starts and how long it runs. The automatic operating mode is
activated using GnAutoEna = On (default). If GnAutoEna = Off, the automatic
operating mode is deactivated.
In addition, the user can also manually start and stop the generator, if required.
Charge State Dependent Start
The time periods t1 and t2 are defined using the "#241.07 GnTm1Str" and "#241.08
GnTm2Str" parameters. The start time for t1 (and thus the end of t2) is defined using
GnTm1Str and the start time for t2 (end of t1) is defined using GnTm2Str.
1
Generator start at GenMan
2
GenMan generator warm up phase begins
3
Generator warm up time
4
GenMan sends ready for connection signal
5
Sunny Island 5048 connects generator
6
Current limit
7
Current is reduced, battery absorption phase
8
GenMan sends generator stop signal (man
Auto!)
9
Sunny Island 5048 disconnects generator
10 Generator power down time expires,
generator stop
11 Stop time has expired
Manual specifications on the Sunny Island 5048 take priority over the
automatic operating mode. If the Sunny Island 5048 is manually stopped
while the automatic operating mode is activated, the Sunny Island 5048
enters into stop/lock operating mode.
If the generator autostart is activated and all the conditions for automatic
operation are satisfied, the Sunny Island 5048 switches back into the start
operating mode following the lockout time (or manual confirmation using
the "#430.02 GnAck" parameter).
Gn
GnReq
GnRun
(DIGIN)
TrfRel
ExtCur
11
10
8
9
7
6
5
4
3
2
1
Summary of Contents for Sunny Island 5048
Page 22: ...The Sunny Island 5048 SMA Technologie AG Page 22 SI5048 11 EE4206 Technical Description...
Page 26: ...Safety Instructions SMA Technologie AG Page 26 SI5048 11 EE4206 Technical Description...
Page 94: ...Battery Management SMA Technologie AG Page 94 SI5048 11 EE4206 Technical Description...
Page 114: ...Connecting External Sources SMA Technologie AG Page 114 SI5048 11 EE4206 Technical Description...
Page 160: ...Contact SMA Technologie AG Page 160 SI5048 11 EE4206 Technical Description...
Page 169: ...SMA Technologie AG Glossary Technical Description SI5048 11 EE4206 Seite 169...
Page 171: ......