Connecting External Sources
Technical Description
SI5048-11:EE4206
Page 109
14.1.9 Stopping the Sunny Island 5048
If the Sunny Island 5048 is stopped by the user, the generator is immediately
disconnected. The generator is then stopped (generator request, GnReq, is disabled).
The power down phase (Cool) is skipped and the system transitions into the stop time.
14.1.10 Failures
Reverse Power
If the reverse power ("#242.13 GnRvPwr" parameter) set for the "#242.14 GnRvTm"
time is exceeded, the generator is disconnected and stopped. The power down time
(Cool) is skipped and the system transitions into the minimum stop time (Lock). After
reverse power, connection is blocked for at least "#230.02 ExtLkTm" or "#242.09
GnStpTmMin".
Generator Failure
If a generator failure is detected (failure on the master phase), the generator is
disconnected immediately and a stop signal occurs on generator. Afterwards, the
system transitions into the minimum stop time (Lock).
Generator Phase Failure
The failure of a phase (e.g. broken fuse) on a slave device is treated as a phase failure.
The slave device then disconnects this phase. If the phase is detected as being available
again, it is reconnected after the warm up time "#242.12 GnWarmTm" has expired.
The phase failure on the master device is treated as a generator failure (see above).
Slave Device Failure
If a slave device fails, the system continues to operate using both the remaining devices
of the cluster as well as those on the generator.
If the generator is started directly at the generator management box or
the generator, it can only be stopped there again. Stopping the Sunny
Island 5048 only disconnects the generator and the system transitions into
the stop time (Lock).
Summary of Contents for Sunny Island 5048
Page 22: ...The Sunny Island 5048 SMA Technologie AG Page 22 SI5048 11 EE4206 Technical Description...
Page 26: ...Safety Instructions SMA Technologie AG Page 26 SI5048 11 EE4206 Technical Description...
Page 94: ...Battery Management SMA Technologie AG Page 94 SI5048 11 EE4206 Technical Description...
Page 114: ...Connecting External Sources SMA Technologie AG Page 114 SI5048 11 EE4206 Technical Description...
Page 160: ...Contact SMA Technologie AG Page 160 SI5048 11 EE4206 Technical Description...
Page 169: ...SMA Technologie AG Glossary Technical Description SI5048 11 EE4206 Seite 169...
Page 171: ......