Troubleshooting/Problem Solving
Technical Description
SI5048-11:EE4206
Page 151
•
The battery fuse (NH fuse (DC)) has been triggered.
Why is it not possible to change the parameters?
•
Has the installer password been entered correctly? Check whether you are
actually in "Installer Level" (see section 10.5 "Entering the Installer Password"
(Page 72)). If necessary, repeat the calculation and entry of the password.
•
You are in the "100-Meters" (measuring data) menu or the "300-Diagnose"
(Diagnosis) menu. You can only read the data values shown here.
•
Some parameters can only be changed in standby mode or in the QCG (see e.g.
the "242.07 GnStrMod" parameter in section 18.2 "Adjustable System
Parameters" (Page 129)). Stop the Sunny Island 5048 as described in section 9.2
"Stopping" (Page 62). Note that this causes a dropout in the stand-alone grid and
the loads are no longer supplied.
Why does the Sunny Island 5048 always connect to the running generator for
a brief time only?
•
The limits for the maximum permissible AC voltage or the minimum permissible
frequency of the generator are too strict (parameter in menu "#242 General
Settings"). Change voltage and/or frequency limits according to the technical
data of your generator.
Why is the stand-alone grid frequency not at 50 Hz?
•
The Sunny Boy inverter is controlled via the frequency (see section 16.3
"Frequency Shift Power Control (FSPC)" (Page 119)).
•
The "AFRA" function of the Sunny Island 5048 is activated (see section 12.5
"Automatic Frequency Adjustment" (Page 84)).
•
Power fluctuations cause frequency deviations.
•
Although the generator runs in droop mode at an average of 50 Hz, the Sunny
Boys can be shut down by the frequency.
Why does the "VAC-Low" error (output voltage too low) also occur when the
Sunny Island 5048 is started?
•
A permanent short circuit exists in the stand-alone grid. Check the AC output
connections of the stand-alone grid (see section 6.3 "AC Connection" (Page 38)).
•
The loads connected to the stand-alone grid are too heavy. The power/electrical
energy of the Sunny Island 5048 is not sufficient to supply the loads. Switch off
some of the loads and restart the Sunny Island 5048.
What happens when a battery cell can no longer be used?
•
Remove the unusable cell from your battery bank. Then start the Sunny Island
5048 and change the battery voltage in the QCG under "New Battery".
Summary of Contents for Sunny Island 5048
Page 22: ...The Sunny Island 5048 SMA Technologie AG Page 22 SI5048 11 EE4206 Technical Description...
Page 26: ...Safety Instructions SMA Technologie AG Page 26 SI5048 11 EE4206 Technical Description...
Page 94: ...Battery Management SMA Technologie AG Page 94 SI5048 11 EE4206 Technical Description...
Page 114: ...Connecting External Sources SMA Technologie AG Page 114 SI5048 11 EE4206 Technical Description...
Page 160: ...Contact SMA Technologie AG Page 160 SI5048 11 EE4206 Technical Description...
Page 169: ...SMA Technologie AG Glossary Technical Description SI5048 11 EE4206 Seite 169...
Page 171: ......