Connecting External Sources
SMA
Technologie AG
Page 96
SI5048-11:EE4206
Technical Description
The following figure principally displays the operation of a generator that has no
remote starting options:
The generator is also always switched off manually. The Sunny Island 5048 then
automatically switches into the operating mode without the generator.
Autostart
This allows autostart generators to be directly integrated. Autostart generators have a
separate internal controller that controls the start procedure.
The Sunny Island 5048 requests the generator using the GnReq signal. If the generator
voltage and frequency are within the set limits (see 14.1.5 "Limits and Power
Adjustment" (Page 105)), the device is synchronized and switched on following the
warm up time.
The Sunny Island 5048 keeps the request signal stable until a disconnection is made
and the set power down time has expired.
The GnReq signal (see 15 "Relay" (Page 115)) is set for signaling the generator
request and can thus be used as an alarm contact. If no request is pending, the
signal is disabled again.
If an internal request is sent while the generator is already running, the signal is
disabled until the generator is externally stopped and the stop time has expired.
A disconnector should be located between the Sunny Island 5048 and the
generator. If the generator is to be stopped, the generator is first manually
disconnected using the disconnector and then it is stopped. This prevents powering
the generator while switching it off.
Autostart generators can also have an internal power down cycle that is only
activated when the request has been disabled. This can extend the power down
time accordingly.
Generator
PE N L
PE N L
PE
AC1
AC2
Sunny Island
PE
N
L
N
C
Inselnetz
PE
N
L
Relay1
Summary of Contents for Sunny Island 5048
Page 22: ...The Sunny Island 5048 SMA Technologie AG Page 22 SI5048 11 EE4206 Technical Description...
Page 26: ...Safety Instructions SMA Technologie AG Page 26 SI5048 11 EE4206 Technical Description...
Page 94: ...Battery Management SMA Technologie AG Page 94 SI5048 11 EE4206 Technical Description...
Page 114: ...Connecting External Sources SMA Technologie AG Page 114 SI5048 11 EE4206 Technical Description...
Page 160: ...Contact SMA Technologie AG Page 160 SI5048 11 EE4206 Technical Description...
Page 169: ...SMA Technologie AG Glossary Technical Description SI5048 11 EE4206 Seite 169...
Page 171: ......