Operation
SMA
Technologie AG
Page 70
SI5048-11:EE4206
Technical Description
Under the menu "#500 Direct Access", you have direct access to settings and display
values.
10.4 Compact Meters
In this special menu, the Sunny Island 5048 simultaneously displays a maximum of four
values. This menu is primarily intended to facilitate the commissioning for the installer.
There is a total of seven different compact meters.
Bat1 (battery values 1)
Bat2 (battery values 2)
Inv (AC values of inverter)
Using the menu #500, you can select the "#241.01 GenAutoEna" parameter, for
example, to activate the generator autostart.
The direct access must be entered as a five-digit number, for example, 24101.
Here, the first 3 digits describe the menu number and the last two describe the
parameter number.
Once the parameter has been set, you exit the setting. Using <ESC>, you return
to Direct Access and you can make additional changes there.
You can select the different displays of the compact meters using the up/down
arrow keys
. Here, you can also use the "Wrap Around" function.
The displays are always shown from the upper left to the lower right.
BatTmp: battery temperature
BatSocErr: estimated error of
the charge state
TotBatCur: total battery
current of cluster
Name of the compact meter
BatSoc: current battery
charge state
Bat1 75.2% 5.6%
8.6A 20.3degC
AptTmRmg: remaining
absorption time
BatChrgVtg: nominal value of
charging voltage
BatChrgOp: active charging
process
BatVtg: battery voltage of
device
Name of the compact meter
Bat2 47.9V 57.5V
Full 05:00:00
InvPwrRt: present reactive
power on the inverter
InvFrq: present frequency on
the inverter
InvPwrAt: present effective
power on the inverter
Name of the compact meter
InvVtg: present voltage on
the inverter
Inv 230V 50.0Hz
-0.62kW 0.10kVAr
Summary of Contents for Sunny Island 5048
Page 22: ...The Sunny Island 5048 SMA Technologie AG Page 22 SI5048 11 EE4206 Technical Description...
Page 26: ...Safety Instructions SMA Technologie AG Page 26 SI5048 11 EE4206 Technical Description...
Page 94: ...Battery Management SMA Technologie AG Page 94 SI5048 11 EE4206 Technical Description...
Page 114: ...Connecting External Sources SMA Technologie AG Page 114 SI5048 11 EE4206 Technical Description...
Page 160: ...Contact SMA Technologie AG Page 160 SI5048 11 EE4206 Technical Description...
Page 169: ...SMA Technologie AG Glossary Technical Description SI5048 11 EE4206 Seite 169...
Page 171: ......