Connecting External Sources
SMA
Technologie AG
Page 98
SI5048-11:EE4206
Technical Description
The following figure principally displays the generator start using the "GenMan"
generator controller.
The GENRDY signal sends a manual generator start at the GenMan to the Sunny Island
5048. The device synchronizes and connects.
If the generator is externally and manually started at the GenMan, Sunny Island 5048
blocks the GnReq signal:
•
Manual stop and start are ignored on the Sunny Island 5048 (operated using the
display and keyboard).
•
Internal requests (e.g. via the battery charge state) are also ignored.
The Sunny Island 5048 disconnects the generator if the GenMan has disabled the
GENRDY signal.
14.1.2 Generator Operation
The Sunny Island 5048 allows automatic operation (depending on charge state or
load) (see 14.1.4 "Automatic Generator Operation" (Page 101)). In addition, manual
operation is also possible.
If the generator has been manually started at the GenMan, it must also be
stopped there.
A manual start directly at the generator is not permitted (see GenMan manual).
Generator
PE N L
PE N L
PE
AC1
AC2
Sunny Island
Relay1
GenMan
DIGIN
--
+
PE
N
L
Batterie
-- +
Gen Freq
Gen
Request
Gen Ready
IGN/Fuel
Relais
NO C
NC
Crank
Relais
NO C
NC
Gen Ready
Relais
NO C
NC
-- +
12 V
Batterie
+
--
Trans-
formator
Anlasser
Zündung /
Vorglühen
NO C
Inselnetz
PE
N
L
Summary of Contents for Sunny Island 5048
Page 22: ...The Sunny Island 5048 SMA Technologie AG Page 22 SI5048 11 EE4206 Technical Description...
Page 26: ...Safety Instructions SMA Technologie AG Page 26 SI5048 11 EE4206 Technical Description...
Page 94: ...Battery Management SMA Technologie AG Page 94 SI5048 11 EE4206 Technical Description...
Page 114: ...Connecting External Sources SMA Technologie AG Page 114 SI5048 11 EE4206 Technical Description...
Page 160: ...Contact SMA Technologie AG Page 160 SI5048 11 EE4206 Technical Description...
Page 169: ...SMA Technologie AG Glossary Technical Description SI5048 11 EE4206 Seite 169...
Page 171: ......