SMA Solar Technology AG
10 Troubleshooting
Operating Manual
SI80H-BE-BEN120810
65
Disconnecting the Generator from Terminal AC1
1. Switch off the off-grid inverter (see Section 5.4).
2. Ensure that the generator is stopped permanently.
3. Disconnect the off-grid inverter from voltage sources (see Section 8).
4. If the terminals AC1 and AC2 are bridged, remove the bridge.
5. If a mobile generator is used, disconnect the generator from terminal AC1.
6. Close the off-grid inverter (see commissioning in the off-grid inverter installation manual).
Starting the Off-Grid System
1. Switch on or connect all miniature circuit-breakers and fuse-switch-disconnectors.
2. Start the off-grid system (see Section 5.2).
Interrupting emergency charge mode
You can interrupt the emergency charge mode, e.g. to add diesel to a generator.
• Press and hold the button.
☑ Emergency charge mode is stopped.
• Press and hold the button.
☑ Emergency charge mode is running.