8 Disconnecting the Off-Grid Inverter from Voltage
Sources
1. Switch off the off-grid system (see Section 5.4).
2. Disconnect the miniature circuit-breaker and the switch-disconnectors in the sub-distributions and
secure against reconnection.
3. Open the switch-disconnector of the BatFuse and secure against reconnection.
6. If you are a skilled person, loosen all the screws of the enclosure lid and remove the lid.
7. Ensure that the DC terminal is disconnected from voltage sources.
8. Ensure that the terminals
AC1 Loads/SunnyBoys
and
AC2 Gen/Grid
are disconnected from
voltage sources.
9. Earth and short-circuit the AC conductors.
10. Cover or safeguard any adjacent live components.
4.
Danger to life due to high voltages
• If you are not a skilled person, inform a skilled person.
• Steps 5 to 10 may only be performed by skilled persons.
5.
Electrostatic discharges can damage the off-grid inverter.
The components inside the inverter can be destroyed by electrostatic discharge.
• Earth yourself before touching any components.