12 Operating Modes
The Sunny Island can be modularly combined with other power sources and must
then operate in different operating modes. This chapter covers both basic grid con-
figurations and the resulting requirements for the Sunny Island and the other compo-
nents in the island grid.
Control of voltage and frequency in the island grid
The Sunny Island can operate in the following operating modes:
•
Grid forming (RUN_U), the Sunny Island keeps the voltage and the frequency
of the grid at a constant level.
•
Grid-tied (RUN_I), the Sunny Island follows the voltage and frequency that is
defined by a further component of the island grid that itself forms the grid.
12.1 Grid-Forming Operation (RUN_U)
In grid forming mode the Sunny Island keeps the grid voltage at a constant sine-
wave voltage and constant frequency. The voltage and frequency is defined in the
“PARGRD“ 3+4 parameters. The Sunny Island then has to provide the necessary
active and reactive power that is required for the control of the grid. All other compo-
nents in the grid then have to operate as grid controlled power generators or con-
sumers.