Sunny Island
Installation & Operating Instructions
BWRI33-12:EE
- 134 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
513_Circ time
s
1
3600
300
Run time of electrolyte circulation (per circulation
process)
516_Circ Qd
%
0,1
50
10
Electrolyte circulation is triggered as soon as the
battery has been charged with the corresponding
ampere hours related to its capacity (cumulative).
518_tset full
d
1
180
14
Time period after which full charge is required.
519_tset equal
d
7
365
180
Time period after which equalizing charge is re-
quired.
520_U float
V
2,2
2,4
2,25
Float charge voltage per cell
521_tVR charge
min
1
600
120
Charging time for normal charge (for gel or fleece
batteries, see also “502_Bat Type”)
522_tVR full
h
1
20
5
Charging time for full charge (for gel or fleece bat-
teries, see also “502_Bat Type”)
523_tVR equal
h
1
48
10
Charging time for equalizing charge (for gel or
fleece batteries, see also “502_Bat Type”)
524_UVR charge
V
2,25
2,6
2,4
Charging voltage for normal charge per cell (for gel
or fleece batteries, see also “502_Bat Type”)
Please follow the instructions of the battery manu-
facturer.
525_UVR charge
full
V
2,25
2,6
2,4
Charging voltage for full charge per cell (for gel or
fleece batteries, see also “502_Bat Type”)
Please follow the instructions of the battery manu-
facturer.
526_UVR charge
equal
V
2,25
2,6
2,4
Charging voltage for equalizing charge per cell (for
gel or fleece batteries, see also “502_Bat Type”)
Please follow the instructions of the battery manu-
facturer.
527_tcharge
min
1
600
90
Charging time for normal charge (for lead-acid bat-
teries, see also “502_Bat Type“)
528_tcharge full
h
1
20
5
Charging time for full charge (for lead-acid batter-
ies, see also “502_Bat Type“)
529_tcharge equal
h
1
48
10
Charging time for equalizing charge (for lead-acid
batteries, see also “502_Bat Type“)
530_Ucharge
V
2,29
2,7
2,55
Charging voltage for normal charge per cell (for
lead-acid batteries, see also “502_Bat Type“)
The value should be reduced to 2,45 V in case an
electrolyte circulation pump is installed.
Please follow the instructions of the battery manu-
facturer.