Sunny Island
Installation & Operating Instructions
BWRI33-12:EE
- 138 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
607_Igen max
A
0
500
0
Max. generator current (per phase),
only applies if “604_GenSet Ctrl” is set accordingly
610_tGen glow
s
1
180
15
Length of time the relay is controlled to glow up the
generator
611_tGen crank
s
1
60
10
Length of time the relay is controlled to crank the
generator
612_tGen warm
s
1
900
15
Warm-up time of generator
613_tGen minrun
min
1
180
5
Minimum run time of generator
614_tGen cool
s
0
900
60
Cooling time of generator
615_tGen stop
s
1
180
10
Length of time the relay is controlled to stop the
generator
616_tGen lock
min
1
180
5
Period of time the generator – after having been
stopped - cannot be restarted via the Sunny Island
(can be shortened by confirmation in the
“GENSET“ (2-2) menu)
617_tGen fail
min
1
180
5
Period of time the generator cannot be restarted
via the Sunny Island after a generator failure (can
be shortened by confirmation in the “GENSET“ (2-
2) menu)
618_tGen faillock
h
1
168
6
Period of time the generator cannot be restarted
via the Sunny Island after a certain number of fail-
ures as defined in “605_GenStRetr“ has occurred
during start-up (can be shortened by confirmation
in the “GENSET“ (2-2) menu)
625_PldL GenOn
%
-100 100
0
Switch-on threshold in % of the nominal power at
one phase for the power-related generator start or
the power-related relais (only K5 or K6). If the re-
lays shall be switched in relation to the power, the
parameters “705_Man K5” and/or “706_Man K6”
must bei set to “LOAD“
626_PldL GenOff
%
-100 100
0
Switch-off threshold in % of the nominal power at
one phase for the power-related generator start or
the power-related relais (only K5 or K6). If the re-
lays shall be switched in relation to the power, the
parameters “705_Man K5” and/or “706_Man K6”
must bei set to “LOAD“
627_PldS GenOn
%
-100 100
0
Switch-on threshold in % of the nominal power
based on the cumulative power within the three-
phase system for the power-related generator start
or the power-related relays (only K5 or K6). If the
relays shall be switched in relation to the power,
the parameters “705_Man K5” and/or “706_Man
K6” must bei set to “LOAD“