Sunny Island
Installation & Operating Instructions
BWRI33-12:EE
- 17 -
SMA Regelsysteme GmbH
•
Keep cables leading to the battery storage as short as possible (DC cabling).
•
Avoid installing in the living area as slight noise emission is possible.
•
Avoid mounting on resonant parts and easily combustible materials (e. g. thin
wooden panels, plaster panels, etc.)
•
Provide accessibility for installation and later service.
•
Installation at level height makes it possible to easily view the display and press
the keys.
Please note the following points in any case:
•
The mounting background must be firm (weight of inverter
approx. 45 kg).
•
The ambient temperature must be between -25 °C and +45 °C.
•
If the Sunny Island is transferred from a cold to a warm place,
wait for a sufficient time (at least 15 minutes) before commis-
sioning so that any moisture condensation that might have oc-
curred can evaporate.
•
A minimum distance of 20 cm must be clear above the inverter
for ventilation, i.e. no cabinets, ceiling, etc.
•
The free air circulation around the case must not be obstructed
to ensure sufficient cooling.
•
If you install the Sunny Island in a cabinet or closet etc., the air
circulation must be sufficient for heat dissipation - provide ex-
ternal ventilation.
•
The heat sink can reach a temperature of more than 80
o
C.
•
Provide a correct position of the battery inverter (see Fig. 3.1
and Fig. 3.2).