Sunny Island
Installation & Operating Instructions
BWRI33-12:EE
- 83 -
SMA Regelsysteme GmbH
“PARBAT“ (3+5)
Name Description
522_tVR full
1 ... 20 h:
Charging time for full charge (with gel or fleece batteries, see
“502_Bat Type”):
523_tVR equal
1 ... 48 h:
Charging time for equal charge (with gel or fleece batteries,
see “502_Bat Type”).
524_UVR charge
2.25 ... 2.6 V:
Charging voltage normal charge per cell (with gel or fleece
batteries, see “502_Bat Type”)
Please follow manufacturer’s instructions.
525_UVR charge
full
2.25 ... 2.6 V:
Charging voltage full charge per cell (with gel or fleece bat-
teries, see “502_Bat Type”).
Please follow manufacturer’s instructions.
526_UVR charge
equal
2.25 ... 2.6 V:
Charging voltage equalizing charge per cell (with gel or
fleece batteries), see “502_Bat Type”)
Please follow manufacturer’s instructions.
527_tcharge
1 ... 600 min:
Charging time for normal charge (with lead acid battery, see
“502_Bat Type”)
528_tcharge full
1 ... 20 h:
Charging time for full charge (with lead acid battery, see
“502_Bat Type”).
529_tcharge equal 1 ... 48 h:
Charging voltage for equalizing charge (with lead acid bat-
tery, see “502_Bat Type”)
530_Ucharge
2.29 ... 2.7 V:
Charging voltage for normal charge per cell (with lead acid
battery, see “502_Bat Type”)
In case of electrolyte circulation pump installed the value should be reduced to
2.45 V. Please follow manufacturer’s instructions.
531_Ucharge full
2.25 ... 2.7 V:
Charging voltage for full charge per cell (with lead acid bat-
teries, see “502_Bat Type”)
In case of electrolyte circulation pump installed the value should be reduced to
2.45 V. Please follow manufacturer’s instructions.
532_Ucharge
equal
2.25 ... 2.7 V:
Charging voltage for equalizing charge per cell (with lead
acid battery, see “502_Bat Type”)
Please follow manufacturer’s instructions.
533_Stdby t beg
0 ... 23 h:
Beginning of period when low-strain operation of battery is
permissible (see “535_Stat StopT”)
534_Stdby t end
0 ... 23 h:
End of period when low-strain operation of battery is permis-
sible (see “535_Stat StopT”)
535_State StopT
L4 ... O3:
In case of deep-cycle discharge the device will switch off to
reduce strain on the battery, if no charging current of a
minimum of 1 A flows into the battery for more than 5 min-
utes within the defined time period (see also “533_Stdby t
beg”, „534_Stdby t end“).
The low battery load mode is always activated, when one battery state lower is
reached. However, from 6 am to 6 pm the Sunny Island attempts to switch on