16 Technical Data
SMA Solar Technology AG
Operating Manual
STPx0-3SE-40-BE-en-10
125
STP5.0-3SE-40
STP6.0-3SE-40
STP8.0-3SE-40
STP10.0-3SE-40
Battery type
1)
Li-ion
Li-ion
Li-ion
Li-ion
Surge category in
accordance with
IEC 60664-1
II
II
II
II
AC output, AC battery-backup system in parallel grid operation mode
STP5.0-3SE-40
STP6.0-3SE-40
STP8.0-3SE-40
STP10.0-3SE-40
Rated power at
230 V, 50 Hz
5000 W
6000 W
8000 W
10000 W
Maximum appar-
ent AC power
5000 VA
6000 VA
8000 VA
10000 VA
Output power <
5 min
6000 W
7200 W
12000 W
12000 W
Output apparent
power < 5 min
6000 VA
7200 VA
12000 VA
12000 VA
Output power <
10 s
10000 W
10000 W
12000 W
12000 W
Output apparent
power < 10 s
10000 VA
10000 VA
12000 VA
12000 VA
Nominal AC volt-
age
3/N/grounding
conductor;
230 V / 400 V
3/N/grounding
conductor;
230 V / 400 V
3/N/grounding
conductor;
230 V / 400 V
3/N/grounding
conductor;
230 V / 400 V
AC grid frequency
50 Hz
50 Hz
50 Hz
50 Hz
Switching time to
battery-backup
operation
2)
< 50 ms
< 50 ms
< 50 ms
< 50 ms
Grid configuration
TN-S
TN-S
TN-S
TN-S
Protective Devices
DC reverse polarity protection
Available
Input-side disconnection point
Available
AC short-circuit current capability
Available
Ground fault monitoring
Available
Grid monitoring
Available
1)
Warning! Danger of fire due to use of non-approved batteries. Only use batteries approved by SMA
Solar Technology AG (technical information with list of approved batteries at www.SMA-Solar.com).
2)
Depending on the configured country data set
Summary of Contents for SUNNY TRIPOWER 10.0 SMART ENERGY
Page 132: ...www SMA Solar com...