12 Troubleshooting
SMA Solar Technology AG
Operating Manual
STPx0-3SE-40-BE-en-10
99
Event number
Message, cause and corrective measures
7324
Wait for update conditions
The testing of the update conditions was not successful. The firmware update
package is not suitable for this inverter.
Corrective measures:
• Retry update.
• Ensure that the selected update file is suitable for this inverter.
• If this message is displayed again, contact the Service.
7330
Condition test failed
Corrective measures:
• Retry update.
• Ensure that the selected update file is suitable for this inverter.
• If this message is displayed again, contact the Service.
7333
Update transport failed
Update file could not be copied to the inverter's internal memory. In the event
of connection with the inverter via Wi-Fi network, a poor connection quality
can be the cause.
Corrective measures:
• Retry update.
• For Wi-Fi connection: Improve the Wi-Fi connection quality (e.g. via Wi-Fi
repeater) or establish connection with the inverter via Ethernet.
• If this message is displayed again, contact the Service.
7337
Battery management system update unsuccessful (|d0|)
Corrective measures:
• Retry update.
• Ensure that the selected update file is suitable for this inverter and the
battery.
• If this message is displayed again, contact the Service.