7 Electrical Connection
SMA Solar Technology AG
Operating Manual
STPx0-3SE-40-BE-en-10
57
☑ The stranded wire can be seen inside the
clamping bracket chamber.
+
4. If the stranded wire is not visible in the chamber, the cable is not correctly inserted and the
connector must be reassembled. To do this, the cable must be removed from the connector.
• Release the clamping bracket. To do so, insert
a screwdriver (blade width: 3.5 mm) into the
clamping bracket and pry the clamping bracket
open.
2
+
1
• Remove the cable and go back to step 2.
+
1
2
5. Push the swivel nut up to the thread and tighten (torque: 2 Nm).
7.6.3
Connecting the PV Array
WARNING
Danger to life due to electric shock from destruction of the measuring device
due to overvoltage
Overvoltage can damage a measuring device and result in voltage being present in the
enclosure of the measuring device. Touching the live enclosure of the measuring device results in
death or lethal injuries due to electric shock.
• Only use measuring devices with a DC input voltage range of 1000 V or higher.