Mains supply impedance is too high
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins
displaying the blink code of: 3 seconds off and then 3 times briefly on. This code is
displayed three times in succession. If the fault is still present, the fault display starts
again from the beginning.
The Windy Boy has detected a fault relating to an unacceptable impedance in the
mains supply. If the Windy Boy frequently displays this fault during mains monitoring,
the cause can be a mains impedance that is too high. An electrician can usually assist
with this problem by increasing the cross section of the mains connection cable. Other
measures can be taken to correct this problem, but they require the agreement and
cooperation of the electricity supplier.
5 s
3 s
1 s
LED on
LED off
The yellow LED
illuminates 3 times
The message is repeated 3 times
and then begins again.
1
2
3
Summary of Contents for Windy Boy 1100
Page 2: ......
Page 4: ...SMA Technologie AG Page 4 WB11_17 11 FE4205 Operating Instructions...
Page 12: ...Safety Information SMA Technologie AG Page 12 WB11_17 11 FE4205 Operating instructions...
Page 36: ...Turbine operation SMA Technologie AG Page 36 WB11_17 11 FE4205 Operating instructions...
Page 38: ...Maintenance and care SMA Technologie AG Page 38 WB11_17 11 FE4205 Operating instructions...
Page 64: ...Stand alone systems SMA Technologie AG Page 64 WB11_17 11 FE4205 Operating instructions...
Page 66: ...Contact SMA Technologie AG Page 66 WB11_17 11 FE4205 Operating instructions...
Page 67: ......