Unit description
SMA
Technologie AG
Page 24
WB11_17-11:FE4205
Operating instructions
Input voltage too high
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins
displaying the blink code of: 3 seconds off and then 4 times briefly on. This code is
displayed three times in succession. If the fault is still present, the fault display starts
again from the beginning.
Immediately disconnect the DC input of the Windy Boy. The pres-
ence of excessive input voltage can lead to irreparable damage!
Make sure that the input voltage never exceeds 400 V.
When the Windy Boy receives an excessive DC input voltage, it automatically
disconnects from the mains network and no longer feeds power into the grid.
When the Windy Boy is in operation, you must always first disconnect the AC
voltage (mains supply) and only then should you disconnect the DC voltage
from the Windy Boy!
5 s
3 s
1 s
1 s
1 s
1 s
The yellow LED
illuminates 4 times
The message is repeated 3 times
and then begins again.
1
2
3
4
LED on
LED off
Summary of Contents for Windy Boy 1100
Page 2: ......
Page 4: ...SMA Technologie AG Page 4 WB11_17 11 FE4205 Operating Instructions...
Page 12: ...Safety Information SMA Technologie AG Page 12 WB11_17 11 FE4205 Operating instructions...
Page 36: ...Turbine operation SMA Technologie AG Page 36 WB11_17 11 FE4205 Operating instructions...
Page 38: ...Maintenance and care SMA Technologie AG Page 38 WB11_17 11 FE4205 Operating instructions...
Page 64: ...Stand alone systems SMA Technologie AG Page 64 WB11_17 11 FE4205 Operating instructions...
Page 66: ...Contact SMA Technologie AG Page 66 WB11_17 11 FE4205 Operating instructions...
Page 67: ......