3.3.2 Critical, faulty operation
A comprehensive safety concept limits the number of critical conditions that can occur
to a single situation:
Input voltage exceeds the permitted value
This is indicated by the following blink-code on the yellow LED:
The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins
displaying the blink code of: 3 seconds off and then 4 times briefly on. This code is
displayed three times in succession. If the fault is still present, the fault display starts
again from the beginning
.
3.3.3 Non-critical, faulty operation
All other fault codes indicate some form of faulty operation, which are not usually
dangerous to people or equipment, but which should nevertheless be investigated
and corrected.
Despite all precautions, it is possible that other faults may occur that cannot be
displayed (e.g. failure of the status display). In order to recognize such faults, the
operator of the system should use the explanations in chapter 3.3.4 "Description of
the operational status” (page 19) to check the plausibility of the displayed status.
Further detailed diagnoses are possible using the communications options detailed in
chapter 8 "Expansions” (page 41).
The presence of excessive input voltage can lead to irreparable
damage! Immediately disconnect the DC input of the Windy Boy
5000 / 6000.
When the Windy Boy 5000 / 6000 receives an excessive DC input voltage, it
automatically disconnects from the mains supply and no longer feeds power
into the grid. When the Windy Boy 5000 / 6000 is in operation, you must
always first disconnect the AC voltage (mains supply) and only then should you
disconnect the DC voltage from the Windy Boy 5000 / 6000!
5 s
3 s
1 s
1 s
1 s
1 s
LED on
LED off
The message is repeated 3 times
and then begins again.
1
2
3
4
The yellow LED
illuminates 4 times
Summary of Contents for Windy Boy 5000
Page 2: ......
Page 4: ...SMA Technologie AG Page 4 WB50_60 11 FE4105 Operating Instructions ...
Page 12: ...Safety information SMA Technology AG Page 12 WB50_60 11 FE4105 Operating instructions ...
Page 28: ...Unit description SMA Technology AG Page 28 WB50_60 11 FE4105 Operating instructions ...
Page 32: ...Maintenance and care SMA Technology AG Page 32 WB50_60 11 FE4105 Operating instructions ...
Page 38: ...Turbine operation SMA Technology AG Page 38 WB50_60 11 FE4105 Operating instructions ...
Page 40: ...Maintenance and care SMA Technology AG Page 40 WB50_60 11 FE4105 Operating instructions ...
Page 66: ...Stand alone systems SMA Technology AG Page 66 WB50_60 11 FE4105 Operating instructions ...
Page 68: ...Contact SMA Technology AG Page 68 WB50_60 11 FE4105 Operating instructions ...
Page 69: ......