General information
SMA
Technology AG
Page 58
WB50_60-11:FE4105
Operating instructions
I-NiTest
mA
0 ... 25000
16000
Activation (16000) and deactivation (0)
of the automatic leakage current
measurement. This parameter only
functions when the Windy Boy is
deactivated (disconnected on the AC
side) or in "Stop" mode.
Inst.-Code
Parameters for mains supply monitoring
can only be changed after entering the
"SMA grid guard" password.
KI-Wind-Reg
0 ... 0,25
0,005
Control speed (only possible in Turbine
mode!)
KP-Wind-Reg
0 ... 0,25
0,117
Control speed (only possible in Turbine
mode!)
P-Wind-Ramp
W/s
10
...
2000
500
Slow startup during mains supply
connection (only possible in Turbine
mode!)
Speicher--
funktion /
Memory
function
Default,
Parameter,
Reset
Betriebsdaten,
Reset Fehler
none
Default parameter: Returns all
parameter values to the factory setting.
Reset Betriebsdaten: Returns all user
level parameter values to the factory
setting.
Reset Fehler: Resets a permanent fault.
Speichern/
store
Permanent,
volatile
Permanent
Permanent: Modified parameters are
stored in the EEPROM and can be used
even when the Windy Boy has been
restarted.
Volatile: Prevents the parameters from
being stored in the EEPROM, the
parameters are stored until the next
restart.
T-Start
sec
5
...
300
10
Start timer for mains supply
synchronization. (only possible in
Turbine mode!)
T-Stop
sec
1 ... 3600
2
Stop timer for stopping operation and
switching off. (only possible in Turbine
mode!)
Uac-Min /
Vac-Min
V
180 ... 300
198
Lower (Uac-Min) and upper (Uac-Max)
limits of the acceptable AC voltage (self
contained power system recognition).
Uac-Max /
Vac-Max
V
180 ... 300
260
U
DC
WindMax
V
1 ... 800
550
U
DC
WindMax represents the highest
point of the function (please read more
about this topic in chapter 6 "Turbine
operation” (page 33)). (only possible in
Turbine mode!)
Name Unit
Value
range
(WB 5000 /
WB 6000)
Factory
settings
(WB 5000
/WB
6000)
Description
Summary of Contents for Windy Boy 5000
Page 2: ......
Page 4: ...SMA Technologie AG Page 4 WB50_60 11 FE4105 Operating Instructions ...
Page 12: ...Safety information SMA Technology AG Page 12 WB50_60 11 FE4105 Operating instructions ...
Page 28: ...Unit description SMA Technology AG Page 28 WB50_60 11 FE4105 Operating instructions ...
Page 32: ...Maintenance and care SMA Technology AG Page 32 WB50_60 11 FE4105 Operating instructions ...
Page 38: ...Turbine operation SMA Technology AG Page 38 WB50_60 11 FE4105 Operating instructions ...
Page 40: ...Maintenance and care SMA Technology AG Page 40 WB50_60 11 FE4105 Operating instructions ...
Page 66: ...Stand alone systems SMA Technology AG Page 66 WB50_60 11 FE4105 Operating instructions ...
Page 68: ...Contact SMA Technology AG Page 68 WB50_60 11 FE4105 Operating instructions ...
Page 69: ......