Operating instructions
9.1.2 Grid connection data
Nominal output power
P
ACnom
5000 W
Peak output power
P
ACmax
5500 W
Nominal output current
I
ACnom
21,7 A
Harmonic distortion of output
current
THD
IAC
< 4 % (P
AC
> 0.5 P
ACnom
)
Operating range, grid voltage
V
AC
198 ... 260 V AC
(180 ... 265 V AC programmable)
Operating range,
grid frequency
f
AC
49.8 ... 50.2 Hz / 59.8 ... 60.2 Hz
(45.5 ... 54.5 Hz programmable)
All-pole isolator grid side
Independent disconnection device
(SMA grid guard)
Phase shift angle
(based on the current's
fundamental frequency)
cos j
1
Overvoltage category
III
Test voltage (50 Hz)
2 kV (1 s routine testing / 60 s type
testing)
Test surge voltage
4 kV (1.2 / 50 µs) type testing
(serial interface: 6 kV)
Own consumption in standby
mode
0.25 W
Summary of Contents for Windy Boy 5000
Page 2: ......
Page 4: ...SMA Technologie AG Page 4 WB50_60 11 FE4105 Operating Instructions ...
Page 12: ...Safety information SMA Technology AG Page 12 WB50_60 11 FE4105 Operating instructions ...
Page 28: ...Unit description SMA Technology AG Page 28 WB50_60 11 FE4105 Operating instructions ...
Page 32: ...Maintenance and care SMA Technology AG Page 32 WB50_60 11 FE4105 Operating instructions ...
Page 38: ...Turbine operation SMA Technology AG Page 38 WB50_60 11 FE4105 Operating instructions ...
Page 40: ...Maintenance and care SMA Technology AG Page 40 WB50_60 11 FE4105 Operating instructions ...
Page 66: ...Stand alone systems SMA Technology AG Page 66 WB50_60 11 FE4105 Operating instructions ...
Page 68: ...Contact SMA Technology AG Page 68 WB50_60 11 FE4105 Operating instructions ...
Page 69: ......