10.1.1 Status Messages
The Windy Boy produces a range of status messages, depending on the mode in which
it is currently operating. The status messages can vary, depending on the type of
communication system you are using.
Name
Explanation
derating
Overtemperature in inverter. The Windy Boy reduces its
performance to prevent the device from overheating. Check whether
the Windy Boy can be installed in a more favorable position with
better ventilation, so that sufficient heat dissipation can be
guaranteed.
Fehler / Error
An error has been detected (see section 10.2 "Error Messages"
(Page 64)).
I-Konst
Operating mode for test purposes
Off Grid
The Windy Boy is in Off Grid mode. This mode is specially
conceived for operation in a stand-alone grid with a Sunny Island
as grid controller. More information about this topic can be
obtained from the Sunny Island operating manual under the
category "Droop Mode".
MPP
The Windy Boy is operating in MPP mode. The Windy Boy takes the
highest possible power output from the PV generator. MPP is the
standard display when operating with normal solar irradiation (PV
operation only!).
Mpp Peak
The Windy Boy is operating in MPP mode above its nominal power
level (PV operation only!).
Netzueb. /
grid mon.
Testing the grid status (grid impedance), relay test, etc. This message
only appears during the startup phase, before the Windy Boy is
connected to the grid. This message mainly appears when there is
little or no wind.
Offset
Offset compensation of the measurement electronics.
Riso
Measurement of the wind turbine system's insulation resistance.
Stoer. / disturb. Fault (see table "Error Messages"). This error occurs for reasons of
safety and prevents the Windy Boy from connecting to the grid. This
status can also be set manually.
Stop
Interruption of operation after a fault. This status can also be set
manually.
Turbine Mode
Factory setting for Windy Boy inverters. The input voltage is
processed according to the programmable power curve. See
section 6 "Turbine Operation" (Page 31).
Summary of Contents for Windy Boy WB 1100LV
Page 2: ......
Page 6: ...Explanation of Symbols Used SMA Technologie AG Page 6 WB1100LV 11 FE2606 User Manual...
Page 10: ...Safety Instructions SMA Technologie AG Page 10 WB1100LV 11 FE2606 User Manual...
Page 28: ...Unit Description SMA Technologie AG Page 28 WB1100LV 11 FE2606 User Manual...
Page 30: ...Setting the Display Language SMA Technologie AG Page 30 WB1100LV 11 FE2606 User Manual...
Page 40: ...Turbine Operation SMA Technologie AG Page 40 WB1100LV 11 FE2606 User Manual...
Page 42: ...Maintenance and Care SMA Technologie AG Page 42 WB1100LV 11 FE2606 User Manual...
Page 50: ...Extensions SMA Technologie AG Page 50 WB1100LV 11 FE2606 User Manual...
Page 54: ...Technical Data SMA Technologie AG Page 54 WB1100LV 11 FE2606 User Manual...
Page 72: ...General Information SMA Technologie AG Page 72 WB1100LV 11 FE2606 User Manual...
Page 74: ...Stand Alone Systems SMA Technologie AG Page 74 WB1100LV 11 FE2606 User Manual...
Page 77: ......