SMA
Technologie AG
General Information
User Manual
WB1100LV-11:FE2606
Page 61
10.1.4 Parameter Settings for Germany
Grayed-out parameters are only displayed in installer mode. The table below contains
the parameters that are applicable in Germany.
Name
Unit
Value Range
Factory Setting
ACVtgRPro
V
230 ... 300 V
253
AntiIsland-Ampl * grd
0 ... 10
0
AntiIsland-Freq * mHz
0 ... 2000
500
Betriebsart
MPP, UKonst,
Stop, Turbine
Mode, Off Grid
Turbine
Default *
GER/VDE
0126-1-1,
SP/RD1663,
GB/G83,
Other, trimmed
GER/VDE0126-1-1
dFac-Max *
Hz/s
0,1 ... 4,0
0,25
dZac-Max *
mohm
0 ... 20000
750
E_Total
kWh
0 ... 200000
0
Fac-delta- *
Hz
0 ... 4,5
2,45
Fac-delta+ *
Hz
0 ... 4,5
0,19
h_Total
h
0 ... 200000
0
I-NiTest *
mA
0 ... 7500
6000
Inst.-Code
KI-Wind-Reg
0 ... 0,25
0,005
KP-Wind-Reg
0 ... 0,25
0,117
Pmax
W
0 ... 1150
1100
P-Wind-Mid
W
10 ... 1100
220
P-Wind-Ramp
W/s
10 ... 600
183
Speicherfunktion
Default
Parameter, Reset
Betriebsdaten,
Reset Fehler
none
T-Start *
s
5 ... 300
10
T-Stop
s
1 ... 3600
2
Summary of Contents for Windy Boy WB 1100LV
Page 2: ......
Page 6: ...Explanation of Symbols Used SMA Technologie AG Page 6 WB1100LV 11 FE2606 User Manual...
Page 10: ...Safety Instructions SMA Technologie AG Page 10 WB1100LV 11 FE2606 User Manual...
Page 28: ...Unit Description SMA Technologie AG Page 28 WB1100LV 11 FE2606 User Manual...
Page 30: ...Setting the Display Language SMA Technologie AG Page 30 WB1100LV 11 FE2606 User Manual...
Page 40: ...Turbine Operation SMA Technologie AG Page 40 WB1100LV 11 FE2606 User Manual...
Page 42: ...Maintenance and Care SMA Technologie AG Page 42 WB1100LV 11 FE2606 User Manual...
Page 50: ...Extensions SMA Technologie AG Page 50 WB1100LV 11 FE2606 User Manual...
Page 54: ...Technical Data SMA Technologie AG Page 54 WB1100LV 11 FE2606 User Manual...
Page 72: ...General Information SMA Technologie AG Page 72 WB1100LV 11 FE2606 User Manual...
Page 74: ...Stand Alone Systems SMA Technologie AG Page 74 WB1100LV 11 FE2606 User Manual...
Page 77: ......