background image

PSI302P – Manual de Instrução e Manutenção

6

As for troubleshooting, the 

PSI302P 

has five indication LEDs and 

PSI302P-2

 has three indication LEDs wich inform its

operation status. A green power supply LED informs that the 

PSI302P

 is appropriately powered. A red overcurrent LED

for each channel, will be lit should any abnormal condition occurs in the field wiring. These LEDs are able to detect
most problems wich may occur in a Fieldbus installation. However, other problems which are not detectable by the
LEDs may occur. Such problems should be: excessive noise introduced by the external power supply; impedance
lower than 20

 in the communication line (consider that such impedance may not be purely resistive and, therefore not

detectable by the overcurrent circuit); and a DC voltage higher than 18 Vdc in the communication line. Such abnormal
conditions may be easily detected by measurement instruments.

Because the 

PSI302P 

is a simply and compact device, it is recommended that repair services be done by replacing

faulty modules instead of electronic components. Some eletronic components used in the 

PSI302P

 are highly accurate

and in the state-of-art, being therefore not easily found in ordinary retail stores. This is the reason why the 

PSI302P 

Fieldbus Power Supply Impedance ha been designed in modules, in order to simplify repair services and the
maintenance of spare parts.

TECHNICAL CHARACTERISTICS

Electrical Characteristics:

Power Supply:

24 to 32 Vdc ±10%

Output Current:

340 mA (máx).

Mechanical Characteristics:

Dimensions (LxPxH): 

40x142x126 mm

Enclosure: 

Metallic box for panel mounting.

Mounting: 

With screws or by means of DIN rail.

DIN rail: 

TS35-DIN EN 50022 or TS32-DIN EN50035

or TS15-DIN EN50045.

Ambient Conditions:

Operation:

T

AMB 

-20°C to 50°C @RH 10% a 95%, without

condensing.

Storage:

T

AMB 

-50°C to 70°C @RH 5% a 95%, without

condensing.

Functional Characteristics:

Input Filter:

Attenuation of 10dB in the input power ripple  @60 Hz.

Impedance Control:

Active impedance control.

Terminator:

Fieldbus terminator.

Safety Characteristics:

Output Overcurrente:

Limitated in 500 mA

Input Fuser:

2,5 A.

Atmospherics Discharges:

Inpout and output protected for surge suppressor.

Intrinsic Safety:

Cannot be used directly.

Aproximately Weight:

 230g

Summary of Contents for PSI302P

Page 1: ...INSTALLATION MANUAL PSI302P PSI302P VERSION 1 FIELDBUS POWER SUPPLY IMPEDANCE PSI302P JUL 02 P S I 3 0 2 P M E FOUNDATION TM ...

Page 2: ...ail smar am wanadoo fr GERMANY Smar GmbH Rheingaustrasse 9 55545 Bad Kreuznach Germany Tel 49 671 794680 Fax 49 671 7946829 e mail infoservice smar de MEXICO Smar México Cerro de las Campanas 3 desp 119 Col San Andrés Atenco Tlalnepantla Edo Del Méx C P 54040 Tel 53 78 46 00 al 02 Fax 53 78 46 03 e mail ventas smar com SINGAPORE Smar Singapore Pte Ltd 315 Outram Road 06 07 Tan Boon Liat Building S...

Page 3: ...s a 100W resistor in series with a 1 mF capacitor required by the standard results in a purely resistive line impedance for a broad frequency range The PSI302P because of the power supplied cannot be used directly in areas requiring intrinsic safety specifications Figure 1 shows the Device Block Diagram The PSI302P can be used in redundancy connecting their output E in parallel When this configura...

Page 4: ... and 4 shows a layout of device PSI302P Fig 1 PSI302P Block Diagram Fig 2 Redundancy of PSI302P Fig 3 Frontal View PSI302P 2 Fig 4 Front View PSI302P 4 PSI302P 4 Eight terminals 3A to 10A to implementation of 4 independent Fieldbus channels and a Dip Switch with 4 switches for interlinked of the internal terminador of the PSI302P 4 The Figure 4 shows a layout of device to verify that 4 Leds of fla...

Page 5: ... to short circuit in the plant or excess of connected equipaments INSTALLATION The PSI302P Fieldbus Power Supply Impedance is a device specially designed for panel installation and it can not be installed in unshetered locations as it can not be exposed to the weather Due to its great thermal dissipation capacity the device may be installed in environments where the maximum temperature reaches up ...

Page 6: ...ing faulty modules instead of electronic components Some eletronic components used in the PSI302P are highly accurate and in the state of art being therefore not easily found in ordinary retail stores This is the reason why the PSI302P Fieldbus Power Supply Impedance ha been designed in modules in order to simplify repair services and the maintenance of spare parts TECHNICAL CHARACTERISTICS Electr...