49
^S007SETBAT
and
^S010SBATPCS16
for “+96V / -96V” battery pack
^S007SETBAT
and
^S010SBATPCS18
for “+108V / -108V” battery pack
^S007SETBAT
and
^S010SBATPCS20
for “+120V / -120V” battery pack
This command will be effective and you should turn off UPS with battery connected to save the
change.
Note
:
If the original battery pack is “+240V/-240V” (Or“+120V/-120V”), and you want to change
to “+192V/-192V” (Or“+96V / -96V”), it is strongly recommended that set the battery pcs to “16”
and save this change firstly, then change the battery pack to “+192/-192” secondly.
Because we
set the rule that when UPS occurs warning code “01”, it’s not able to save the change
. So if you
change the battery pack firstly, UPS maybe occur warning code “01”, it will not able to save the
change and it will be dangerous for that charging voltage does not match the actual battery Pcs.
e, For example, we use the USB cable to send the
battery pcs setting
command.
Open the communication Tool and you will see the following interface
Click the “Refresh”, you will see “USB…” and ”2400” at the appropriate location.
Enter the “
^S007SETBAT
” command and click “Send”. When it return “D006
ACK
…”, this setting
is successful. Enter“
^S010SBATPCS16
”and click “Send” to set the battery pcs. When it return
“D006
ACK
…”, this setting is successful. Or enter the “
^S007SETBAT
” command and
“
^S010SBATPCS20
”.
Summary of Contents for SBOL50KTIII-3
Page 2: ...2 ...
Page 10: ...10 n 5 Picture of the UPS 30k picture single input dual input ...
Page 11: ...11 30k UPS inner picture 60K picture ...
Page 12: ...12 60K picture 60K unit inner picture ...
Page 13: ...13 Front panel Rear panel Left panel 100K 200K picture ...
Page 14: ...14 Right side panel Top side panel 100K 200K picture ...
Page 38: ...38 HV30KL LV15KL Single Input Mode ...