10
AUDIBLE ALARM
Specifications
ENVIRONMENT
CONFORMANCE
INTERFACE
INDICATORS
PHYSICAL
BATTERY
PROTECTION
OUTPUT
<40 dBA (1 meter from surface) (AC model) <45 dBA (DC model)
1000 / 600
1400 / 840
2000 / 1200
6-NEMA 5-15R UPS
Red LED lighting
INPUT
Audible Noise
Ambient Operation
Warranty
Safety
Low Battery
AC Mode
Receptacles
Input Inlet
Dimensions D x W x H In. (mm)
Shipping Weight (Lbs. / Kg.)
Net Weight (Lbs. / Kg.)
Back-up Time (Minutes)
Half Load
Protection
Typical Recharge Time
Battery Type
Short Circuit
Tel / Fax / Modem / DSL
Unit Input
Transfer Time
Voltage Regulation (AVR)
Frequency (on battery)
Voltage (on battery)
Capacity VA / W
Frequency
Spike Protection
Voltage
0-90% humidity non-condensing 0-40 deg C
AC cord (5-15P)
cUL, UL
DB9-RS232
15.70 x 5.70 x 8.07 (399 x 145 x 205)
25.25 / 11.5
26.85 / 12.18
28.35 / 12.86
UPS output cuts off immediately or input circuit breaker protection
Circuit breaker for overload & short circuit protection
Automatic self-test & discharge protection, replace battery indicator
4-8 milli seconds, including detection time
AVR automatically increases output voltage 17% above input voltage if -9% to -25% of nominal.
AVR decreases output voltage 15% below input voltage if +9% to +25% of nominal
Simulated sine wave at 120V ±10%
<10V Normal Mode <0.5V Common Mode
89 - 145VAC
50 or 60Hz ±1%
RJ11/45
10 hours (to 90% of full capacity) after complete discharge
Sealed, maintenance-free lead acid
220/230/240V models available. Consult factory for specifications and features.
Specifications and features subject to change without notice.
UPSWING for Windows
Software detects power failure, battery low, schedule UPS on/off, AC power status display, bat / load level display
Overload
UPS automatic shutdown if overload exceeds:
1) Line mode: 110% of nominal at 5 minutes, 120% immediately
2) Battery mode: 110% of nominal at 10 seconds, 120% immediately
Optional Software
UPSWING PRO for Novell, SCO UNIX, Linux, Sun, Solaris
Two years for the SBP unit. Four years pro-rated battery warranty. $25,000 Lifetime Connected Equipment Protection Warranty
8
10
5
SBP1000TBF
22.80 / 10.4
24.86 / 11.28
26.36 / 11.96
1040 Joules
Lowest Pass through Voltage
The 1st. green LED lighting, and the 2nd. to 5th. green LED gradually lighting indicating load level 1
Backup Mode
Fault
The 1st. green LED flashing, and the 2nd. to 5th. green LED gradually lighting indicating battery capacity
Beeps every second
Backup Mode
Beeps every 10 seconds
Overload
Beeps every 0.5 seconds
Fault
Continuously Beeps
Battery Replace
Beeps every 2 seconds
50 or 60Hz±1% (auto sensing)
SBP1400TBF
SBP2000TBF