Version 6.00
Date of editing: 16.09.2022
r.
Page 1 of 30
Technical documentation
KWP-L
1438
SMAY Sp. z o.o.
22
CSWU: 1438-CPR-0509
DWU: 011-CPR-2017
EN 15650:2010
Fire damper
type: KTP-LE,KWP-LS
Nominal activation
conditions/sensitivity:
Closing/opening during
the test at the right time
Pass
Response time/Closure time:
Pass
Reliability:
50 cycles. <120s
Fire resistance:
Fire integrity - E
Fire insulation - l
Smoke leakage - S
Mechanical stability
(under E)
Maintenance of the cross section (under E)
EI 120 (ve h
o
i
↔
o) S
EI 90 (ve i
↔
o) S
EI 60 (ve i
↔
o) S
EI 30 (ve i
↔
o) S
Durability:
Opening and closing cycle test (1)
KWP-LE: 10 000 cycles, <120s (1)
KWP-LS: 300 cycles, <120s (1)