Technical documentation
KWP-L
7.4.
INSTALLATION TECHNOLOGY
–
CONSTRUCTIONS OF GREAT THICKNESS
Figure 14. Installation method of fire dampers KWP-L in constructions of great thickness
In rigid and flexible wall construction and in ceiling with thickness less or equal to 140 mm, KWP-L fire dampers are
mounted in such a way that the damper baffle axis matches the axis of the structure.
Whereas in case of walls and ceilings with thickness higher than 140 mm: the KWP-L fire dampers are mounted in
such a way, that the damper building boundary i.e. 210 mm, is maintained (as in figure 14).