Version 6.00
Date of editing:
16.09.2022
r.
Page 6 z 11
Installation manual
WKP-O
II.
INSTALLATION TECHNOLOGY - PROMADUCT CHANNEL
After setting the fire damper as described, and build it in wall, duct made of PROMATECT-L500 boards with 50 mm
thickness must be installed. The band around the duct must be made by PROMATECT-L500, with 50 mm thickness and
60 mm width. Connection of damper and the wall, and damper with the band must be made by K84 glue. The sides of
the duct and the band must be connected by using 4,2x90
–
4,8x120 screws.
Figure 5. Installing method of WKP-O fire dampers with PROMAT boards duct.