HRX-OM-W058
Chapter 5 Display and setting of various functions
HRS-R Series
5.9
Offset function
5-25
5.
Select offset temperature from the table below with [
▲] key or [▼] key, and confirm by
pressing “SEL”.
Table 5.9-3
List of set value
Set value
Explanation
Initial
(Default setting)
Setting and checking are not available when
offset mode setting is OFF.
Centigrade
to
Sets offset temperature.
Temperature unit is Centigrade : Setting unit is
0.1
o
C
Temperature unit is Fahrenheit : Setting unit is
0.1
o
F
Fahrenheit
to
6.
Press the [MENU] key once.
Return to the main screen (screen displaying the circulating fluid temperature).
PV
SV
This function controls the offset temperature to the circulating fluid
discharge temperature
Control range of the circulating fluid temperature is 5.0
o
C to 40.0
o
C
(41.0
o
F to 104.0
o
F).
When the circulating fluid temperature is set to 5.0
o
C (41oF) and the
offset temperature to -20.0
o
C (-36.0
o
F), the offset temperature is
automatically adjusted to 0.0oC (0.0
o
F) depending on the offset
mode.