HRX-OM-W058
Chapter 5 Display and setting of various functions
HRS-R Series
5.16
Alarm customize function
5-37
Table 5.16-2
List of set alarm customize function(2/2)
Display
Item
Contents
Initial value
(Default setting)
Unused
- - - -
*1
Unused
- - - -
*1
Temperature alarm
Monitoring method
One alarm monitoring method can be selected
from four methods for AS04 "Detection temp for
the circulating fluid discharge temp. increase"
and AS06 "Detection temp. for circulating fluid
discharge temp. drop".
0
Monitoring start timer
Alarm will not be generated during the set period
of time after starting operation. Alarm monitoring
starts when it reaches the set time.
- - - -
Range over
Detection timer
After starting the alarm monitoring, the alarm will
not be generated right away and will be kept not
generated for the set period of time for AS04
"Detection temp for the circulating fluid discharge
temp. increase" and AS06 "Detection temp. for
circulating fluid discharge temp. drop", when the
temperatures goes out of the set range.
5
*1
:
This function is not available for this product.
1.
Press and hold the [MENU] key for approx. 2 sec.
Repeat pressing the key until the setting screen for alarm buzzer sound [
]
appears on the digital display.
Low tank level Setting and checking
2.
Press the [SEL] key once.
The set screen of changing of low tank level is displayed on the digital display.
3.
Select changing of low tank level from the table below with
[▲] key or [▼] key, and
confirm by pressing “SEL”.
Table 5.16-3
List of set value
Set value
Explanation
Initial value
(Default setting)
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
○
Note
)
On option J (automatic water fill function) model, Abnormal Pump Operation (AL07) could be happened when
you select “A.rUn” mode.
PV
SV
PV
SV
[
MENU
]
Press and
hold
[
MENU
]
Press and
hold
[
MENU
]
Press and
hold
PV
SV
PV
SV
PV