-28-
No.EX
※※
-OME0014-F
Specification
■
Specifications
General specification
Item
Specification
Operating ambient temp.
-10 to +50
o
C
Operating ambient humidity
35 to 85%RH (No dew condensation)
Storage ambient temp.
-20 to +60
o
C
Withstand voltage
500 VAC for 1 min.
Insulation resistance
500 VDC 10 M
Ω
or more
Operating environment
No corrosive gas
Pollution degree
Pollution degree 3
Enclosure IP67
Applicable standard
UL/CSA, CE
Electrical specification
Item
Specification
Power for SI/Input
Block Current
consumption
19.2 to 28.8 VDC
Depending on the number of Input Block stations and sensor specifications:
1.1 A or less
(Inside SI unit: 0.1 A or less)
Power Voltage
range, current
consumption
Power for solenoid
valve Current
consumption
22.8 to 26.4 VDC
Depending on number of solenoid valve station and specifications:
2.0 A or less
Output type
Source / PNP (negative common)
Connection load
Solenoid valve with surge voltage suppressor of 24 VDC and 1.5 W or less
(manufactured by SMC)
Insulation type
Photo coupler type
Solenoid valve
connection
specification
Residual Voltage
0.3 VDC or less
Communication specification
Item
Specification
Protocol
PROFIBUS DP (EN50170, EN50254)
BUS
.
Interface EIA
RS-485
Communication form
Token passing
Transmission speed
9.6/19.2/45.45/93.75/187.5/500/1500/12000 kbps
Transmission media
STP cable
Connect node
Max. 125 station
Network topology
Bus, tree, star
Cable length
Max. 23 km (Repeater needed)
Freeze mode
Available
Sync mode
Available
Input point
Max. 32 points
Output point
Max. 32 points
ID number
1408 hex (SW setting mode)
1409 hex (HW setting mode)
Applicable solenoid valves
Representative series
Applicable series
VQC series
VQC1000, VQC2000, VQC4000
SV series
SV1000, SV2000, SV3000 (Tie-rod base manifold)
S0700 series
S0700
Summary of Contents for EX250-SPR1