EX500-TF2Z135EN

 

Page 1 of 2 

 

Instruction Manual 

Gateway unit – PROFIBUS DP compatible 

Series EX500-GPR1A-X20

 

 

 

 

 

 

 

 

The intended use of the Gateway unit is for connection to SI units and 
input devices for the control of pneumatic valves.

 

1 Safety Instructions 

These safety instructions are intended to prevent hazardous situations 
and/or equipment damage. These instructions indicate the level of 
potential hazard with the labels of “Caution,” “Warning” or “Danger.” 
They are all important notes for safety and must be followed in addition 
to International Standards (ISO/IEC)

 *1)

, and other safety regulations. 

*1)

 ISO 4414: Pneumatic fluid power - General rules relating to systems. 

ISO 4413: Hydraulic fluid power - General rules relating to systems. 
IEC 60204-1: Safety of machinery - Electrical equipment of machines. 
(Part 1: General requirements) 
ISO 10218-1: Manipulating industrial robots -Safety. etc. 

  Refer  to product catalogue, Operation Manual and Handling 

Precautions for SMC Products for additional information. 

  Keep this manual in a safe place for future reference. 

 

Caution 

Caution indicates a hazard with a low level of risk which, if 

not avoided, could result in minor or moderate injury. 

 

Warning 

Warning indicates a hazard with a medium level of risk 

which, if not avoided, could result in death or serious injury. 

 

Danger 

Danger indicates a hazard with a high level of risk which, if 

not avoided, will result in death or serious injury. 

Warning 

 

Always ensure compliance with relevant safety laws and 
standards. 

  All work must be carried out in a safe manner by a qualified person in 

compliance with applicable national regulations. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

2 Specifications 

General specifications 

Item 

Specifications 

Ambient temperature 

5 to 45 

o

Ambient humidity 

35 to 85% RH (no condensate) 

Ambient storage temperature   -25 to +70 

o

Withstand voltage 

1000 VAC applied for 1 minute 

Insulation resistance 

500 VDC, 2 M

Ω

 or more 

Weight 

470 g 

Electrical specifications 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

3 Name and function of parts 

 

 

No 

Part 

Description 

1  Fieldbus connector 

Connection to PROFIBUS DP 

2  Power supply connector  Connection for power supply. 

3  Connector (COM A) 

Connection to SI units (manifold valve) 
or input units using a branch cable. 

4  Connector (COM B) 

5  Connector (COM C) 

6  Connector (COM D) 

7  LED Display 

Displays the unit status. 

8  Switch cover 

Set the address and bus terminator 
switches under the cover. 

9  FE terminal (M3) 

Functional Earth (FE). 

 
 
 

4 Installation 

4.1  Direct mounting 

Secure in position using 4 x M5 screws, 15 mm minimum thread length. 

 

4.2  Wiring connections 

 

Communication Connector 

Select the appropriate cables to mate with the connectors on the SI 
unit.  The PROFIBUS  DP  connection has 2 ports, BUS IN and BUS 
OUT, and both ports can be used for connection. 

M12 5-pin Plug / Socket (B-coded) 

Connector 

Pin No. 

Signal name 

BUS IN 

BUS OUT 

 

 

N.C. 

RxD/TxD-N 

N.C. 

RxD/TxD-P 

Plug 

Socket 

Shield 

 

 

Power Supply Connector 

Connect the power supply to the power supply connector on the 
Gateway unit. With this cable, power is supplied to the output devices 
(such as solenoid valve) and the input devices and for control. 

 

 

 
 
 
 
 
 

The M12 connector cable for fieldbus and power supply connections 
has two types, Standard M12 and SPEEDCON compatible. If both 
plug and socket have SPEEDCON  connectors, the cable can be 
inserted and connected by turning it a 1/2 rotation.  
A standard connector can be connected to a SPEEDCON connector. 

 

  Both single and two power supply systems can be adopted, however 

the wiring should be made separately (for solenoid valves / outputs 
and for input and control) for either system. 

 

Branch Connector 

Connect  SI units (solenoid valves)  and input devices  to  the 
communication  connectors  (COM  A  -  D)  using  an  M12  (8-pin) 
connector cable (EX500-AC###-S#P#). 
As each cable contains power supply wiring, there is no need to 
supply power to the SI unit (solenoid valves)  or input devices 
separately. 

 

Warning 

  Be sure to fit a seal cap (EX9-AWTS) on any unused connectors. 

Proper use of the seal cap enables the enclosure to maintain IP65 
specification. Tightening torque: 0.1 N•m. 

4.3  Ground Connection 

  Connect the FE terminal (M3) to ground. 

  Individual grounding should be provided close to the product with a 

short cable to assure the safety and noise resistance of the system. 

  Resistance to ground should be 100 

Ω 

or less. 

4 Installation (continued) 

4.4  Environment 

Warning 

  Do not use in an environment where corrosive gases, chemicals, salt 

water or steam are present. 

  Do not install in a location subject to vibration or impact in excess of 

the product’s specifications.  

  Do not mount in a location exposed to radiant heat that would result 

in temperatures in excess of the product’s specifications. 

 

5 Setting 

5.1  Switch setting 

  The switches should only be set with the power supply turned OFF. 

  Open the switch protection cover and set the switches with a small 

flat blade screwdriver. 

  Be sure to set the switches before use. 

  After setting the switches close the protective  cover and tighten the 

screws with the specified tightening torque of 0.6 N•m. 

 

 

 
 

 

 

 

 

 

 

  The node address can be set in the range 0 – 125. 

  The number of available nodes is up to 32 stations per branch, or 126 

stations with a repeater. 

 

 

Bus terminator switch (SW4) 

A bus terminator is required at both ends of the PROFIBUS DP bus 
segment.  
Switch SW4 ON if the Gateway unit is at the end of the bus segment. 

 

 

5.2  Configuration 

An applicable GSD file is required to configure the Gateway unit for the 
PROFIBUS  DP  network.  Download the latest GSD  file from the SMC 
website (URL

https://www.smcworld.com

). 

Product number 

GSD files 

EX500-GPR1A-X20 

Smc_140e.gsd 

 
Technical documentation giving detailed configuration information can 
be found on the SMC website (URL: 

https://www.smcworld.com

)

 
 
 
 
 
 

ORIGINAL INSTRUCTIONS 

Item 

Specifications 

Power supply for control and 
input 

24.0 VDC ±10%, 3.0 A 

Power supply for solenoid 
valves 

24.0 VDC +10%/-5%, 3.0 A 

Current consumption 

Input device and SI unit control: 2.8 A 
Gateway internal circuit: 0.2 A 

No. of Inputs / Outputs 

64 Inputs / 64 Outputs 

Communication specifications 

Item 

Specifications 

Protocol 

PROFIBUS DP (EN 50170) 

Bus interface 

EIA RS-485 

Device type 

Slave 

Communication speed 

9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 kbps 
1.5 / 3.0 / 6.0 / 12 Mbps 

Occupied area 

64 inputs / 64 outputs max. 

Configuration file 

GSD file 

ID number 

140E (Hex) 

Low level bus specifications 

Item 

Specifications 

No. of branches for inputs 

4 branches for input (8 per branch) 

No. of branches for outputs 

4 branches for output (16 per branch) 

Communication method 

Dedicated protocol for SMC, 750 kbps 

Branch current for inputs 

0.7 A max. per branch 

Branch current for outputs 

0.65 A max. per branch (for EX500-S001) 
0.75 A max. per branch (for EX500-Q#01) 

Branch cable length  

5 m max. per branch (10 m total max.) 

 

M12 5-pin Socket (A-coded) 

Connector 

Pin No. 

Signal name 

 

0 V (solenoid valves) 

24 V (solenoid valves) 

0 V (control and input) 

24 V (control and input) 

FE 

 

 

 

 

 

Address setting

 

SW3 (x100) 

SW2 

SW1 

Node Address 

x10 

x1 

N.C. 

0 (default) 

98 

99 

100 

101 

125 

 