background image

LED Display

The status display LED displays the power supply and communication
status.

Display

ST(M)

PWR

PWR(V)

MS

Content

Displays the diagnostic status of the unit.

Displays the status of the power supply
voltage for control and input.

Displays the status of the power supply
voltage for outputs.

Displays the module status.

NS

Displays the network status.

•SI unit common status

Content

The power supply for control and input is
OFF.

LED display 

OFF.

The unit is in normal operation.

Green LEDs are ON.

A component failure inside the SI unit.

Red ST(M) LED is ON.

The power supply voltage for control and
input is abnormal.

Red PWR LED is ON.

The power supply voltage for output is
abnormal.

Red PWR(V) LED is ON.

Troubleshooting

Refer to the LED Display. Refer to the SMC website
(URL http://www.smcworld.com) to obtain more detailed information
about troubleshooting.

Setting and Adjustment

Refer to the SMC website (URL http://www.smcworld.com) to obtain
more detailed information about setting and adjustment.

Diagnostic

Commissioning

•Parameter Setting
•Hardware Configuration (EDS file)
•I/O Map

Outline with Dimensions

Refer to the product catalogue or SMC website
(URL http://www.smcworld.com) to obtain more detailed information
about outline dimensions.

Refer to the SMC website (URL http://www.smcworld.com) to obtain
more detailed information about diagnostics.

Refer to the SMC website (URL http://www.smcworld.com) to obtain
more detailed information about these settings.

A unit other than the SI unit has been
detected.

Green ST(M) LED is

flashing.

Either of the following conditions:
•The valve ON/OFF counter has

exceeded the set value.

•The valve is short circuited or

disconnected.

Red ST(M) LED is flashing.

Either of the following conditions:
•Connection error between units has

occurred.

•Configuration memory error has

occurred.

Red/Green ST(M) LED is

flashing alternately.

A component failure inside the SI unit.

Red MS LED is ON.

The power supply for control and input is
OFF, or IP address is not set.

NS LED is OFF.

•EtherNet/IP

TM

status

Content

The power supply for control and input is
OFF.

LED display 

MS LED is OFF.

Either of the following conditions:
•The unit has not been configured

correctly.

•Fieldbus is idling.

Green MS LED is flashing.

The unit is in normal operation.

Green MS LED is ON.

Recoverable error.

Red MS LED is flashing.

Specification

Maintenance

•Maintenance should be performed according to the Safety Instructions.
•Perform regular maintenance and inspections.

There is a risk of unexpected malfunction.

•Do not use solvents such as benzene, thinner etc. to clean each unit.

They could damage the surface of the body and erase the markings on
the body.
Use a soft cloth to remove stains.
For heavy stains, use a cloth soaked with diluted neutral detergent and
fully squeezed, then wipe up the stains again with a dry cloth.

Refer to the SMC website (URL http://www.smcworld.com) to obtain
more detailed information about maintenance.

Contacts

AUSTRIA

(43) 2262 622

8

NETHERLANDS

(31) 20 531 

8888

 

BELGIUM

(32) 3 355 1464 

NORWAY

(47) 67 12 90 20 

CZECH REP.

(420) 541 424 611 

POLAND

(4

8

) 22 211 9600 

DENMARK

(45) 7025 2900 

PORTUGAL

(351) 21 471 1

88

0

FINLAND

(35

8

) 207 513513 

SLOVAKIA

(421) 2 444 56725 

FRANCE

(33) 1 6476 1000 

SLOVENIA

(3

8

6) 73 

88

5 412

GERMANY

(49) 6103 4020 

SPAIN

(34) 945 1

8

4 100 

GREECE

(30) 210 271 7265 

SWEDEN

(46) 

8

 603 1200 

HUNGARY

(36) 23 511 390 

SWITZERLAND

(41) 52 396 3131 

IRELAND

(353) 1 403 9000 

UNITED KINGDOM

(44) 190

8

 563

888

 

ITALY

(39) 02 92711

URL http://www.smcworld.com (Global) http://www.smceu.com (Europe)

Specifications are subject to change without prior notice from the manufacturer.
© 2010 SMC Corporation All Rights Reserved.

LED Display (Continued)

ON

1

2

3

4

5

6

7

8

Settings3

Settings1

ON

1 2 3 4 5 6 7 8

Settings2

ON

1 2 3 4 5 6 7 8

•IP address setting switch

192.16

8

.0.254

:

192.16

8

.0.1

1

192.16

8

.1.254

2

OFF

:

ON

OFF

ON

:

OFF

ON

OFF

:

OFF

ON

3

ON

:

OFF

ON

Settings2

:

192.16

8

.1.1

DHCP mode 

1

Remote Control

mode 

2

:

ON

ON

OFF

:

OFF

ON

OFF

:

ON

ON/OFF

ON/OFF

:

OFF

ON

OFF

Settings1

8

4

5

ON

:

OFF

ON

ON

:

OFF

ON

6

ON

:

OFF

ON

:

OFF

ON

OFF

:

OFF

ON

OFF

:

OFF

ON

OFF

7

8

ON

:

OFF

ON

ON

:

OFF

ON

:

OFF

ON

OFF

:

OFF

ON

OFF

•V_SEL switch: The number of outputs (size) occupied by the SI unit is

selected.

Content

Number of valves = 32 outputs

Number of valves = 24 outputs

Number of valves = 16 outputs

Settings3

1

Number of valves = 

8

 outputs

SI unit output data size

4 byte (Default setting)

3 byte

2 byte

1 byte

2

OFF

OFF

ON

ON

OFF

ON

OFF

ON

•Diagnostics switch: Allocates the diagnostic data to the input data.

Content

Input data only (Default setting)

Input data + System diagnosis

Input data + System dia
Unit diagnosis (Up to 10 units)

Settings3

3

Diagnostic size set

for the input

0 byte

4 byte

6 byte

4

OFF

OFF

ON

OFF

ON

OFF

Mode

0

1

2

•EtherNet/IP

TM

communication setting switch.

Automatic

10 Mbps, half duplex

10 Mbps, full duplex

100 Mbps, half duplex

Settings3

100 Mbps, full duplex

Communication speed full

duplex/half duplex setting

6

OFF

ON

ON

ON

ON

7

8

ON/OFF

OFF

OFF

ON

ON/OFF

OFF

ON

OFF

ON

ON

1: The mode to obtain IP address from DHCP server. Obtained IP address is

lost when the power supply is cut.

2: The mode to respond to the commands from the BOOTP/DHCP Server

provided by Rockwell Automation.

Enable DHCP: IP address etc. can be obtained from BOOTP/DHCP Server.

If the power is supplied again in this state, information
including IP address is obtained again.

Disable DHCP: IP address etc. cannot be obtained from BOOTP/DHCP

Server.
If the power is supplied again with this condition, previous
setting can be held.

•HOLD/CLEAR switch: Sets the output status when the fieldbus has a

communication error or is in idling.

Content

Output is OFF. (Default setting)

Holds the output.

Settings3

5

OFF

ON

IP address

Setting and Adjustment  (Continued)

Connection timeout.

Red NS LED is flashing.

IP address is duplicated. 

Red NS LED is ON.

The unit received an IP address, but
connection is not established.

Green NS LED is flashing.

Connection is established.

Green NS LED is ON.

EX600-TFN25

-10 to 50 

o

C

(Max. surrounding air temperature rating: 50 

o

C)

Connected load

-20 to 60 

o

C

Operating temperature

range

For use in Pollution Degree 2 Environment

(UL50

8

)

Pollution degree

24 VDC 1.5 W (SMC)

Solenoid valve with LED and circuit protection

10 to 57 Hz: constant amplitude 0.75 mm p-p

57 to 150 Hz: constant acceleration 49 m/s

2

for 2 hours each in direction X, Y and Z

respectively (De-energized)

Vibration resistance

147 m/s

2

3 times each in directions of X, Y and

Z respectively (De-energized)

Impact resistance

24 VDC Class2, 2 A

Power
supply

24 VDC Class2, 2 A

Output

Control and input

Storage temperature

range

Refer to the product catalogue or SMC website
(URL http://www.smcworld.com) to obtain more detailed information