background image

EX600-W 

Series

Specifications

Trademark

EtherNet/IP

®

 is a registered trademark of ODVA. Inc.

Base Module: 

EX600-WEN

m

Item

Specifications

EtherNet/IP
communication

Communication protocol

EtherNet/IP™ (Conformance test version: Composit 12)

Transmission medium (cable)

Standard Ethernet cable (CAT5 or higher, 100BASE-TX)

Communication speed

10 Mbps/100 Mbps

Communication method

Full duplex/Half duplex

Configuration file

EDS file

*

1

IP address setting

Manual/BOOTP, DHCP

Device information

Vendor ID: 7 (SMC Corp.)

Device type: 12 (Communication Adaptor)

Product code: 186

Topology

Star, Bus, Ring (DLR), Line, Tree

QuickConnect function

Applicable

DLR function

Applicable

Web server function

Applicable

Wireless 
communication

Protocol

SMC original protocol (SMC encryption) V.1.0

Radio wave type (spread)

Frequency Hopping Spread Spectrum (FHSS)

Frequency

2.4 GHz (2403 to 2481 MHz)

Number of frequency channels

79 ch (Bandwidth: 1.0 MHz)

Communication speed

250 kbps

Communication distance

10 m (Depending on the operating environment)

Radio Law certificate

Refer to the SMC website for the latest information regarding in which countries 

the product is certified.

Electrical

For control/input
(US1)

Power supply voltage

24 VDC 

±

10%

Current consumption

150 mA or less

For output
(US2)

Power supply voltage

24 VDC 

±

10%

Max. supply current

4 A

Input/Output

Number of 
inputs

System input size

Max. 1280 points together with the registered remote modules

Input size

Max. 128 points (increase or decrease by 16 points)

Number of 
outputs

System output size

Max. 1280 points together with the registered remote modules

Output size

Max. 128 points (increase or decrease by 16 points)

Analog 
input/output

AD refresh time

10 ms or less (the input connected to the base module)

0.1/0.2/0.5/1/2/5/10/30/60 s

 (the input connected to the remote module)

*

2

DA refresh time

10 ms or less (the output connected to the base module)

0.1/0.2/0.5/1/2/5/10/30/60 s

 (the output connected to the remote module)

*

2

Valve output

Output type

EX600-WEN1: Source/PNP (−COM)
EX600-WEN2: Sink/NPN (+COM)

Number of outputs

Max. 32 points (0/8/16/24/32 points)

Connected load

Solenoid valve with surge voltage suppressor of 24 VDC and 1.5 W or less (manufactured by SMC)

Number of remote modules connected

Max. 127 units (0/15/31/63/127 units)

Number of connected EX600 I/O units

Max. 9 EX600 series I/O units (I/O = 128. I/O above 128 cannot be recognized.)

General

Enclosure

Conforms to IP67 (with manifold assembled)

Ambient temperature (Operating temperature)

−10 to +50

°

C

Ambient temperature (Storage temperature)

−20 to +60

°

C

Ambient humidity

35 to 85% RH (No condensation)

Withstand voltage

500 VAC for 1 minute between external terminals and metallic parts

Insulation resistance

10 M

Ω

 or more (500 VDC between external terminals and metallic parts)

Vibration resistance

Conforms to EN 61131-2

 f 

<

 8.4 Hz 3.5 mm

8.4 

 f 

<

 150 Hz 9.8 m/s

2

(Excludes valve manifold)

Impact resistance

Conforms to EN 61131-2

147 m/s

2

, 11 ms

(Excludes valve manifold)

Standards

CE marking

Weight

300 g

NFC
communication

*

3

Communication standard

ISO/IEC 14443B (Type-B)

Frequency

13.56 MHz

Communication speed

20 to 100 kHz (I2C)

Communication distance

Up to 1 cm

*

1  The configuration file can be downloaded from the SMC website: https://www.smcworld.com

*

2  Varies depending on the wireless communication status and the surrounding environment

*

3  The NFC communication RFID tag of the 13.56 MHz passive type

27

Summary of Contents for EX600-W Series

Page 1: ...sub Spring type terminal block Communication cables not required Reduced wiring work space and cost Minimized disconnection risk Communication distance Communication speed Response time Compact Type EXW1 100 m 1 Mbps 2 ms 250 kbps 5 ms Modular Type EX600 W 10 m 250 kbps 5 ms For the EXW1 construction it depends on the operating environment Communication distance speed Response time Compact Type EX...

Page 2: ... antennas Communication is possible with an external antenna even when the wireless base remote is installed in a metal shielded location such as in a control panel box External antenna Compact wireless base Wireless base Wireless remote Wireless base Wireless remote Wireless remote Control box Control panel Compact remote Compact EXW1 Compact EXW1 Modular EX600 W Noise in electronic circuits Inte...

Page 3: ...selected hopping communication is established on 79 ch by default Frequency hopping Event communication system A stable wireless environment is established using an original protocol which is not affected by interference Interference from other wireless equipment is reduced Wireless communication is performed only when there is a variation in the information thereby suppressing the frequency of ra...

Page 4: ...web screen Log data of the number of wireless communication retries and of the received signal strength can be generated from the web screen and downloaded in a CSV file The wireless environment and installation location can be optimized by checking the number of retries and the received radio wave intensity Refer to the logging function on page 4 The log files showing the number of retries or the...

Page 5: ...473 Frequency MHz Communication trial rate RSSI from base to remote Received signal strength indicator RSSI dBm RSSI from remote to base Wireless System Compact Type EXW1 Series Modular Type EX600 W Series Logging function The following information is saved in the internal memory of the product It can be downloaded and visualized from the web function or the setting software IO Configurator Receiv...

Page 6: ...tive Others Indicator light Relay Buzzer Solenoid valve Valve manifold Plug lead Vacuum unit Output devices Input Output device Input devices Fieldbus The compact EXW1 and the modular EX600 W can be mixed 1 Wireless base Wireless remote Mixed input and output loading Input Output 1 When they are mixed the communication speed response time is limited to the EX600 W s specifications Refer to the sys...

Page 7: ... Configuration Examples Applicable functions Frequency channel select F C S Applicable Communication speed Select from 1 Mbps or 250 kbps Response speed Select from 2 ms or 5 ms Communication distance Approx 100 m Depends on the operating environment External antenna Applicable Applicable functions Frequency channel select F C S Not applicable Communication speed 250 kbps Response speed 5 ms Commu...

Page 8: ... Communication connectors required q w Wireless system Base 1 unit Remote 15 units 1 line Connector at one end 1 location Existing Wired system SI unit 15 units 1 line Connector at one end 14 lines Connector at both ends 29 locations The max I O points of the base remote module is limited to 128 points Connection interchangeability between EX600 series SI units is maintained The replacement of wir...

Page 9: ...g parts Minimized disconnection risk Shorter time for establishing communication startup time Communication is possible by placing the external antenna outside the control panel when the unit is installed in a metal box etc Minimized disconnection risk Smaller diameter communication cable tubing Power supply line only Power supply line Communication line For rotary tables Wired system 8 ...

Page 10: ...ss remote input Compact wireless base Compact Type EXW1 Series Accessories Made to Order Modular Type EX600 W Series Wireless System Compact wireless remote output Remote module Base module External antenna set Compact Type EXW1 Series qPower Supply Cable p 19 wCommunication Cable p 20 eField wireable Communication Connector p 21 rSeal Cap 10 pcs p 21 tExternal Antenna Set p 21 yPower Supply Conne...

Page 11: ...nput Y Output M Input Output Compact wireless Compact wireless Base Remote Compact Wireless Base External antenna set External antenna set Input Output Input Output Compact Wireless Remote EXW1 BMJA B E EXW1 RD M P E3 B E 5 The antenna specification selected cannot be changed after purchase 6 The external antenna set cannot be used for the internal antenna specification 7 An external antenna set i...

Page 12: ...7 units 15 31 62 127 units CC Link Communication Specifications EXW1 BMJAm Item Specifications Protocol CC Link Ver 1 10 Ver 2 00 Station type Remote device station Device type Wireless equipment Code 0x4B Station number 1 to 64 Communication speed 156 625 kbps 2 5 5 10 Mbps Configuration file CSP file 1 Occupation area Number of inputs outputs Max 896 inputs 896 outputs Max number of occupied sta...

Page 13: ...ts 2 points connector Type NPN COM Max sensor supply current 0 3 A connector 2 A unit ON current Typ 5 mA OFF current 2 mA or less ON voltage 11 V or more OFF voltage 5 V or less Overcurrentprotection detectionfunction Applicable Electrical Specifications Output Type Item Specifications US1 for control input power supply voltage range 24 VDC 10 US2 for output power supply voltage range 24 VDC 10 I...

Page 14: ...q w e 2 x R 1 SLD 2 3 DG 4 1 2 3 4 CC Link BUS connector IN OUT Internal circuit 1 24 V US1 2 NC 3 0 V US1 4 NC qPower supply connector wBUS IN eBUS OUT DB DA 5 SLD DG DB DA NC FE RF RF Filter Radio Act compliance label The metal housing part of the RF SMA coaxial connector is connected to 0 V US1 EXW1 Series Dimensions Parts Description EXW1 BMJAm qPower supply connector No Signal M12 4 pin plug ...

Page 15: ...nna Accessory RF cable ø5 1 5 m Accessory Bracket Accessory External antenna set Included only for antenna specification B Part no EXW1 EA1 2 x ø4 5 Wireless System Compact Type EXW1 Series Dimensions Parts Description EXW1 RDMmmmm PWR Power supply connector q w e r Pin no Description 1 24 V US1 2 24 V US2 3 0 V US1 4 0 V US2 INPUT Connector for input device connection q w e r Pin no Description 1...

Page 16: ...uded only for antenna specification B Part no EXW1 EA1 2 x ø4 5 2 x ø4 5 30 15 20 US1 RF Input I F Short circuit protection Short circuit protection FE RF Filter 4 N C 3 2 N C 1 PWR 1 24 V US1 2 n 1 3 0 V US1 4 n 7 0 INPUT x 8 The metal housing part of the RF SMA coaxial connector is connected to 0 V US1 Internal circuit EXW1 Series Dimensions Parts Description EXW1 RDXmmmm PWR Power supply connec...

Page 17: ...tion Short circuit protection Filter 4 3 2 1 PWR 1 COM US2_24 V 2 n 1 3 COM US2_24 V 4 n 7 0 OUTPUT x 8 The metal housing part of the RF SMA coaxial connector is connected to 0 V US1 Internal circuit Wireless System Compact Type EXW1 Series Dimensions Parts Description EXW1 RDYmmmm PWR Power supply connector q w e r Pin no Description 1 24 V US1 2 24 V US2 3 0 V US1 4 0 V US2 OUTPUT Connector for ...

Page 18: ...ceived power level of 2 Green Flashing 2 Hz There are connected remotes with a received power level of 1 Red Flashing All the remotes that support protocol V 1 0 are not connected Orange Flashing All the remotes that support protocol V 2 0 are not connected OFF The remote module is not registered 6 W NS Wireless communication connection status indication Green ON All the remote connections are nor...

Page 19: ...detection of the US2 for output power supply Red ON Non restorable error is detected OFF The US1 for control input power supply is OFF 3 W SS Radio wave receiving intensity Green ON The received power level is 3 Green Flashing 1 Hz The received power level is 2 Green Flashing 2 Hz The received power level is 1 Red Flashing Protocol V 1 0 wireless communication is not established Orange Flashing Pr...

Page 20: ... 3 2 1 5 36 3 L 22 5 50 Marker tag M12 SPEEDCON 28 ø5 9 Marker tag ø14 8 PCA 1564927 Straight 2 m PCA 1564930 Straight 6 m PCA 1564943 Right angled 2 m PCA 1564969 Right angled 6 m qPower Supply Cable M12 connector The shape of the M12 connector is B coded Reverse key Straight connector type Angled connector type Item Specifications Cable O D ø5 9 mm Conductor nominal cross section 0 34 mm2 AWG22 ...

Page 21: ...gnal name CC Link Metal parts Shield Metal parts 22 5 ø7 7 8 8 33 1 33 1 L ø14 4 29 6 35 ø14 8 32 5 35 Marker tag Marker tag M12 SPEEDCON M12 SPEEDCON Metal parts Metal parts For CC Link PCA 1567720 Socket PCA 1567717 Plug wCommunication Cable Cable length 10000 mm Refer to page 23 Made to Order Item Specifications Cable O D ø7 7 mm Conductor nominal cross section Data pair 0 5 mm2 AWG20 Drain 0 3...

Page 22: ... The external antenna set cannot be used for the internal antenna specification It is not possible to use the external antenna set without connecting it with the external antenna specification EX9 AWTS For M12 Be sure to mount a seal cap on any unused communication connectors Otherwise the specified enclosure cannot be maintained One cap is included with the wireless base EXW1 BMJAm rSeal Cap 10 p...

Page 23: ...or ZB AXT661 13A 14A m AWG24 ø1 4 ZS 28 C 2 ZS 28 CA 5 ZL ZM SY100 30 4A m 0 3 ø1 55 ZS 28 C 4 ZS 28 CA 5 ZK2 ZK2 LVmm A 0 2 AWG24 ø1 4 ZS 28 C 2 ZS 28 CA 5 Input Pressure Z ISE10 20 0 15 AWG26 ø1 0 ZS 28 C 1 ZS 28 CA 2 PS1000 0 18 ø0 96 ZS 28 CA 2 Auto switch D M9 0 15 ø0 88 ZS 28 CA 1 Flow PF2M AWG26 0 13 ø1 ZS 28 CA 2 Auto switch Input Output devices Valve Power supply e CON Part Nos List Part ...

Page 24: ... Marker tag 22 5 44 5 Marker tag M12 SPEEDCON ø7 7 10000 ø14 8 Socket connector pin arrangement A coded Normal key 4 3 2 1 1 Connections Terminal no Core wire color Signal name CC Link 1 Shield SLD 2 White DB 3 Yellow DG 4 Blue DA 1 Number of holes 5 Total number of pins 4 Item Specifications Cable O D ø7 7 mm Conductor nominal cross section Datapair 0 5 mm2 AWG20 Drain 0 34 mm2 AWG22 Wire O D Inc...

Page 25: ...minal block 32 pins Symbol Description P PNP N NPN Symbol Number of inputs Connector B 8 inputs M12 connector 5 pins 4 pcs C 8 inputs M8 connector 3 pins 8 pcs C1 8 inputs M8 connector 3 pins 8 pcs With open circuit detection D 16 inputs M12 connector 5 pins 8 pcs E 16 inputs D sub connector 25 pins F 16 inputs Spring type terminal block 32 pins Symbol Description P PNP N NPN P P P D B F Digital I...

Page 26: ... connector Symbol Power supply connector Specifications 2 M12 5 pins B coded IN 3 7 8 inch 5 pins IN 4 M12 4 5 pins A coded 1 IN OUT 5 M12 4 5 pins A coded 1 IN OUT Mounting method Symbol Description Note Nil Without DIN rail mounting bracket 2 With DIN rail mounting bracket For SV S0700 VQC series 3 With DIN rail mounting bracket For SY series When the end plate U side is used the symbol for the ...

Page 27: ...tible Negative common M12 connector IN OUT pin arrangement 1 I O unit 2 stations SY3100 5U1 3 sets 2 position single part no SY3200 5U1 2 sets 2 position double part no EX600 DXPD 1 set I O unit part no Stations 1 EX600 DYPB 1 set I O unit part no Stations 2 EX600 ED4 1 set EX600 WEN1 1 set EX600 EU1 1 set EX600 ED4 1 set EX600 DXPD 1 set EX600 DYPB 1 set EX600 WSV1 1 set EX600 EU1 1 set SS5Y3 10S...

Page 28: ... Max 128 points increase or decrease by 16 points Analog input output AD refresh time 10 ms or less the input connected to the base module 0 1 0 2 0 5 1 2 5 10 30 60 s the input connected to the remote module 2 DA refresh time 10 ms or less the output connected to the base module 0 1 0 2 0 5 1 2 5 10 30 60 s the output connected to the remote module 2 Valve output Output type EX600 WEN1 Source PNP...

Page 29: ... connected to the remote module 2 DA refresh time 10 ms or less the output connected to the base module 0 1 0 2 0 5 1 2 5 10 30 60 s the output connected to the remote module 2 Valve output Output type EX600 WPN1 Source PNP COM EX600 WPN2 Sink NPN COM Number of outputs Max 32 points 0 8 16 24 32 points Connected load Solenoid valve with surge voltage suppressor of 24 VDC and 1 5 W or less manufact...

Page 30: ...al Enclosure Conforms to IP67 with manifold assembled Ambient temperature Operating temperature 10 to 50 C Ambient temperature Storage temperature 20 to 60 C Ambient humidity 35 to 85 RH No condensation Withstand voltage 500 VAC for 1 minute between external terminals and metallic parts Insulation resistance 10 MΩ or more 500 VDC between external terminals and metallic parts Vibration resistance C...

Page 31: ...nector Port 1 ID label EtherNet MAC address Wireless PID Product ID Wireless System Modular Type EX600 W Series Dimensions Connector for EtherNet IP Port 1 Port 2 M12 4 pin D coded socket Pin no Description 4 3 2 1 1 Tx 2 Rx 3 Tx 4 Rx Base Module EX600 WENm 30 EXW1 Series Accessories Made to Order EX600 W Series Accessories Technical Data Specific Product Precautions ...

Page 32: ...ireless PID Product ID 56 4 Model label 8 106 Marker groove 8 56 4 ID label Wireless PID Product ID Model label Radio Act compliance label FCC ID label Area close to NFC antenna 47 55 2 10 7 106 EX600 W Series Dimensions PROFINET IO BUS connector Port 1 Port 2 M12 4 pin D coded socket Pin no Description 4 3 2 1 1 TD 2 RD 3 TD 4 RD Base Module Remote Module EX600 WPNm EX600 WSVm 31 ...

Page 33: ... 0V for control input 3 24V for control input 4 0V for output 4 0V for control input Power supply connector PWR OUT M12 5 pin socket A coded Configuration EX600 ED4 Pin arrangement 1 EX600 ED5 Pin arrangement 2 Pin no Description Pin no Description 5 4 1 3 2 1 24V for control input 1 24V for output 2 24V for output 2 0V for output 3 0V for control input 3 24V for control input 4 0V for output 4 0V...

Page 34: ... Cap 12 3 21 76 25 45 6 EX600 W Series Dimensions EX600 ED3 EX600 EU1 Power supply connector PWR 7 8 inch 5 pin plug Configuration Pin no Description 4 3 2 5 1 1 0 V for output 2 0 V for control input 3 FE 4 24 V for control input 5 24 V for output EX600 ED3 EX600 EU1 EXW1 NT1 EXW1 AB1 Option For EX600 W Order a fixing bracket End Plate D side End Plate U side NFC Reader Writer Fixing Bracket 33 ...

Page 35: ...Dflashes 1Hz There are connected remotes with a received power level of 2 GreenLEDflashes 2Hz There are connected remotes with a received power level of 1 Red LED flashes No remotes are connected OFF The remote module is not registered 5 W NS Wireless communication connection status Green LED is ON All remote modules are connected correctly Green LED flashes There are unconnected remote modules Re...

Page 36: ...on is not established The power supply of the PROFINET controller is OFF There is a defective connection in the communication cable between the PROFINET controller and the base module The PROFINET controller or the base module has broken down The PROFINET controller setting and the device name of the base module are mismatched 4 W SS Radio wave receiving intensity For communication from remote to ...

Page 37: ...shes No remotes are connected Red LED is ON No remotes are connected Non restorable error in wireless communication Red Green Wireless communication connection is under construction Pairing Orange LED is ON Forced output mode OFF The base module is not registered 4 MS Remote module system status Green LED is ON Remote module is normal Red LED flashes Restorable error is detected LED flashes when o...

Page 38: ...tor For EX600 ED2 0Power Supply Cable M12 connector For EX600 ED4 5 EX600 ZMV1 For the SV S0700 and VQC series EX600 ZMA3 For the SY and JSY series EX600 ZMV2 For the SY and JSY series EX600 W Series Accessories Optional Parts EX600 ZMA2 For the SV S0700 and VQC series This bracket is used for the end plate of DIN rail mounting Enclosed parts Round head screw M4 x 20 1 pc P tight screw 4 x 14 2 pc...

Page 39: ...ure cannot be maintained The signal name of I O device and each unit address can be entered and mounted on each unit EX600 ZT1 yMarker 1 sheet 88 pcs tSeal Cap 10 pcs The end plate is for use when the manifold valve is not connected Enclosed parts Round head screw M4 x 6 2 pcs eEnd Plate U side End plate End plate mounting position U side Mounting method Symbol Description Note Nil Without DIN rai...

Page 40: ... compatible with AWG22 16 iPower Supply Field wireable Connector 7 8 inch Straight connector type Angled connector type Applicable Cable Item Specifications Cable O D ø12 0 to 14 0 mm Wire gauge Stranded wire cross section 0 34 to 1 5 mm2 AWG22 to 16 Item Specifications Cable O D ø5 9 mm Conductor nominal cross section 0 34 mm2 AWG22 Wire O D Including insulator 1 27 mm Min bending radius Fixed 59...

Page 41: ...hape of the M12 connector is A coded Normal key Straight connector type Cable length L 010 1000 mm 050 5000 mm Connector specification S Straight A Angled Connections Angled connector type SPEEDCON Cable length L 1401804 1500 mm 1401805 3000 mm 1401806 5000 mm Cable length L 1557769 3000 mm Item Specifications Cable O D ø5 mm Nominal cross section 0 3 mm2 AWG22 Wire diameter Including insulator 1 ...

Page 42: ...e RD Yellow TD Orange TD Connections Terminal no Wire guide color ø6 5 ø14 8 47 3 5000 50 M12 SPEEDCON PCA 1446566 Plug EX9 AC 020 EN PSRJ Plug RJ 45 connector Item Specifications Cable O D ø6 5 mm Conductor nominal cross section AWG22 Wire O D Including insulator 1 55 mm Min bending radius Fixed 45 5 mm Cable length L 010 1000 mm 020 2000 mm 030 3000 mm 050 5000 mm 100 10000 mm 1Communication Cab...

Page 43: ...h L 005 500 mm 010 1000 mm 020 2000 mm 030 3000 mm 050 5000 mm 100 10000 mm Item Specifications Cable O D ø6 5 mm Conductor nominal cross section 0 34 mm2 AWG22 Wire O D Including insulator 1 55 mm Min bending radius Fixed 19 5 mm Item Specifications Cable O D ø6 5 mm Conductor nominal cross section 0 34 mm2 AWG22 Wire O D Including insulator 1 55 mm Min bending radius Fixed 19 5 mm EX9 AC 005 EN ...

Page 44: ...or For sensor PCA 1557769 Cable with M12 connector 4 pins 3 m PCA 1557772 Cable with M8 connector 3 pins 3 m Field wireable connector For sensor PCA 1557730 Field wireable connector M8 3 pins Plug Piercecon connection PCA 1557743 Field wireable connector M12 4 pins Plug QUICKON ONE connection SPEEDCON PCA 1557756 Y connector For sensor PCA 1557785 Y connector 2 x M12 5 pins M12 5 pins SPEEDCON PCA...

Page 45: ...ype EXW1 Series Iceland Ireland Italy Estonia Austria Netherlands Cyprus Greece Croatia Sweden Spain Slovakia Slovenia Czech Republic Denmark Germany Hungary Finland France Bulgaria Belgium Poland Portugal Malta Latvia Lithuania Liechtenstein Romania Luxembourg U K Switzerland Turkey Norway U S Canada South Korea Japan Vietnam NFC Reader Writer EXW1 NT1 Iceland Ireland Italy Estonia Austria Nether...

Page 46: ...dustry Canada s license exempt RSSs Operation is subject to the following two conditions 1 This device may not cause interference and 2 This device must accept any interference including interference that may cause undesired operation of the device 3 When operating the product please be sure to maintain a separation distance of at least 20 cm between your body excluding fingers hands wrists ankles...

Page 47: ...sures to prevent unexpected operation and malfunction 4 Contact SMC beforehand and take special consideration of safety measures if the product is to be used in any of the following conditions 1 Conditions and environments outside of the given specifications or use outdoors or in a place exposed to direct sunlight 2 Installation on equipment in conjunction with atomic energy railways air navigatio...

Reviews: