Alarm

Operation Display Panel

This product can display eight types of alarm codes and they can be read using serial communication.
In addition, it can relay output as an alarm contact output when an alarm is generated.

RUN/STOP key

For switching the control status (RUN/STOP)

1st line

Displays the current temperature value 
[PV]
Displays the alarm code when an alarm 
is generated

RUN display

Turns on during control status (RUN status)

2nd line

Displays the setting temperature value 
[SV] and each selected input value

 key (UP key)

Increases set data

ALARM display

Turns on when the unit is alarming

MODE key

For switching the screen
It can be switched between the parameter 
screen and operation mode screen when 
it is pressed for two seconds.

 key (DOWN key)

Decreases set data

Maintenance

The maintenance of this unit can only be performed by returning it to be repaired at one of SMC’s sites. As a rule, SMC will not 
conduct on-site maintenance.

Alarm

Alarm code

Alarm description

Operation 

status

Main reason

AL0

Memory error

Stop

There is an abnormality with the memory data in the controller due to a high level of noise.

AL1

Controller error

Stop

There is an abnormality with the data in the controller due to a high level of noise.

AL2

Temp. sensor disconnection alarm

Stop

The temperature sensor has been disconnected or short-circuited.

AL3

Temp. sensor short circuit alarm

Stop

There is a short-circuit in the temperature sensor.

AL4

Temp. sensor high temp. error alarm

Stop

The temperature sensor has exceeded the high temperature cutoff setting.

AL5

Temp. sensor low temp. error alarm

Stop

The temperature sensor has exceeded the low temperature cutoff setting.

AL6

Low fluid level alarm

Stop

The amount of circulating fluid in the tank has dropped.

AL7

Thermostat alarm

Stop

The thermostat has activated due to clogging of the heat sink of the filter or product, or failure 
of the fan or pump.

9

HEF 

Series

Summary of Contents for HEF Series

Page 1: ...94 s a 41 s Compared with the existing product HECR002 Time to change the circulating fluid temperature from 30 C to 20 C when the circulating fluid IN and OUT are directly connected Now only takes ab...

Page 2: ...se design Noise Level Sound level Noise level reference Sound example 20 dB Whisper The sound of leaves touching each other or the sound of snow falling 30 dB Very quiet Suburbs late at night or the s...

Page 3: ...emperature sensor and out from the circulating fluid outlet The heat dissipation air flow direction is as shown in Figure 2 Air is taken from the front of the Thermo con and discharged from the rear D...

Page 4: ...m Bumper Circulation Between Gas Generation Analyzer and JacketedVessel Application Examples Peltier type Chiller Thermo con Compact Type Air cooled HEF Series C mount lens F mount lens Microscope C m...

Page 5: ...ecifications p 6 Cooling Capacity p 7 Heating Capacity p 7 Pump Capacity Thermo con Outlet p 7 Dimensions p 8 Operation Display Panel p 9 Alarm p 9 Maintenance p 9 Option High Pressure Pump Mounted p...

Page 6: ...down to 20 C Water bath Example When cooling the object below a certain temperature in certain period of time Cooled substance total volume V 2 L Cooling time h 15 min Cooling temperature difference...

Page 7: ...4 Fluid contact material Stainless steel EPDM NBR Ceramics PPE PPS Carbon PP POM Electrical system Power supply 24 VDC 10 Power consumption 12 5 A Peak current 18 A Alarm Refer to Alarm Communication...

Page 8: ...rox 20 W For the high pressure pump Option the heating capacity increases by approx 10 W Pump Capacity Thermo con Outlet Circulating fluid Water 0 18 0 16 0 14 0 12 0 10 0 08 0 06 0 04 0 02 0 0 1 1 5...

Page 9: ...ignal input 5 SG 6 Output cutoff alarm open when alarm occurs 7 Common for output cutoff alarm 8 RUN STOP signal input 9 RS 485 BUS Power Cable Accessory Connector J42FSC 02V KX J S T Mfg Co Ltd made...

Page 10: ...be repaired at one of SMC s sites As a rule SMC will not conduct on site maintenance Alarm Alarm code Alarm description Operation status Main reason AL0 Memory error Stop There is an abnormality with...

Page 11: ...customer s piping resistance Cooling capacity is reduced by approx 20 W due to the heat generation from the pump P HEF002 A6 P High pressure pump mounted Options have to be selected when ordering the...

Page 12: ...ecifications Power supply input 100 240 VAC Single phase 50 60 Hz Max 3 9 A DC output 24 VDC Max 12 5 A Operating environment Ambient temperature 0 to 40 C Humidity 20 to 80 RH no condensation DC outp...

Page 13: ...s less than these values the thermo con will not be able to provide precise control and the repeated cooling and heating operations may cause it to fail 7 A magnet driven pump is used as the circulati...

Page 14: ...Copper Cu mg L 0 1 or less Sulfide ion S2 mg L Should not be detected Ammonium ion NH4 mg L 0 1 or less Residual chlorine Cl mg L 0 3 or less Free carbon CO2 mg L 4 0 or less 11 If there is a point w...

Page 15: ...of SMC products with production equipment for the manufacture of weapons of mass destruction WMD or any other weapon is strictly prohibited 2 The exports of SMC products or technology from one countr...

Page 16: ...c hu Ireland 353 0 14039000 www smcautomation ie sales smcautomation ie Italy 39 03990691 www smcitalia it mailbox smcitalia it Latvia 371 67817700 www smc lv info smc lv Lithuania 370 5 2308118 www s...

Reviews: