HRX-OM-X084
Chapter 3 Transport and Setting Up
HRR Series
3.3 Installation
3-13
Table 3-6 Contact input/output pin number
PIN
no
Application
Division
Initial value
(Default setting)
1
DC 24V output
Output
2
DC 24V output
Output
3
DC 24V output
Output
4
Contact input signal 1
Input
None
5
COM of contact output signal 1
Output
6
COM of contact output signal 2
Output
7
COM of contact output signal 3
Output
8
None
-
9
24 COM output
Output
10
24 COM output
Output
11
COM of contact input signal
Output
12
Contact input signal 2
Input
None
13
Contact output signal 1
Output
Run status signal (N.O type)
14
Contact output signal 2
Output
Remote signal (N.O type)
15
Contact output signal 3
Output
Alarm signal (N.C type)
Internal
circuit
1k
Ω
4.7k
Ω
1k
Ω
4.7k
Ω
11
4
12
6
14
7
15
8
5
13
3
10
2
9
1
DC24V
24COM
This product
Your system
DC24V output
24COM output
DC24V output
24COM output
DC24V output
MAX 0.5A
COM of contact input signal
Contact input signal 1:OFF
(Default unsetting)
Contact input signal 2:OFF
(Default unsetting)
COM of contact output signal 1
Contact output signal 1:Run status
(Default unsetting)
COM of contact output signal 2
Contact output signal 2:Remote
(Default unsetting)
COM of contact output signal 3
Contact output signal :Alarm
(Default unsetting)
None Do not connect.
Fig 3-5 Contact input/output
Summary of Contents for HRR010-A-10 Series
Page 14: ...HRX OM X084 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Page 46: ...HRX OM X084 Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRR Series 3 24...
Page 120: ...HRX OM X084 Chapter 6 Option 6 5 Option Z HRR Series 6 6...
Page 165: ......