HRX-OM-X084
Chapter 5 Display and Setting of Various Functions
HRR Series
5.3 List of parameters
5-9
5.3.6 Alarm Setting Menu
Table
5.3-6
Alarm setting menu Parameter list
1
Can only be set with option DM(Electric conductivity control function,DI water (pure water) piping).
2
Can only be set with air-cooled type.
3
Not displayed for options Z and Z1.
4
Not displayed for option Z.
5 For option T1.
Initial value
Select/setting range
TOP
screen
-
AL.ST
-
MENU
-
No.1
screen
Changing of "AL09
:
Circulating fluid
discharge pressure rise"
FLT
WRN/FLT
HI.PRS
⇒
ALARM
-
No.2
screen
Setting for "AL09
:
Circulating fluid
discharge temperature rise"
0.5
0.35
5
0.05 to 0.50
0.05 to 0.40
5
HI.PRS
MPa
No.3
screen
Detection time for "AL09
:
Circulating
fluid discharge temperature rise"
5
0 to 60
HI.PRS
⇒
TIME
SEC
No.4
screen
Changing of "AL10
:
Lower flow rate"
3
WRN
OFF/WRN/FLT
LO.FL
⇒
ALARM
-
No.5
screen
Setting for "AL10
:
Lower flow rate"
3
4.0
2.0 to 15.0
LO.FL
LPM
No.6
screen
Detection time for "AL10
:
Lower flow rate"
3
5
0 to 600
LO.FL
⇒
TIME
SEC
No.7
screen
Changing of "AL12
:
Electric conductivity
control pressure rise alarm" (μS/cm) *1
WRN
OFF/WRN
DI.HI
⇒
ALARM
-
No.8
screen
Setting for "AL12
:
Electric conductivity
control pressure rise alarm" (μS/cm) *1
45.0
0.4 to 46.0
DI.HI
-
No.9
screen
Changing of "AL.13
:
NOT TEMP READY alarm"
OFF
OFF/WRN/FLT
TEMP
⇒
READY
⇒
ALARM
-
No.10
screen
Output setting of "AL.13
:
NOT TEMP READYalarm"
ON
OFF/ON
TEMP
⇒
READY
⇒
OUT.P
-
No.11
screen
Changing of "AL14
:
Circulating fluid
temperature rise alarm"
OFF
OFF/WRN/FLT
TEMP
⇒
OUT.HI
⇒
ALARM
-
No.12
screen
output setting of "AL14
:
Circulating fluid
temperature rise alarm"
ON
OFF/ON
TEMP
⇒
OUT.HI
⇒
OUT.P
-
No.13
screen
Changing of "AL15
:
Circulating fluid temperature drop"
OFF
OFF/WRN/FLT
TEMP
⇒
OUT.LO
⇒
ALARM
-
No.14
screen
Output setting of "AL15
:
Circulating fluid
temperature drop"
ON
OFF/ON
TEMP
⇒
OUT.LO
⇒
OUT.P
-
No.15
screen
Changing of "AL11
:
Ambient temperature
out of range alarm" *2
OFF
OFF/WRN/FLT
AMB
⇒
TEMP
⇒
ALARM
-
No.16
screen
Upper limit of "AL11
:
Ambient temperature
out of range alarm" *2
40.0
10.0 to 45.0
AMB
⇒
HI.TEMP
℃
No.17
screen
Lower limit "AL11
:
Ambient temperature
out of range alarm" *2
10.0
5.0 to 40.0
AMB
⇒
LO.TEMP
℃
No.18
screen
Changing of "AL04
:
Water leakage"
4
WRN
OFF/WRN/FLT
WATER
⇒
LEAK
⇒
ALARM
-
No.19
screen
Changing of "AL25
:
Contact input signal
detection 1"
FLT
OFF/WRN/FLT
INP1
⇒
ALARM
-
No.20
screen
"AL25
:
Contact input signal detection 1"
reading delay timer
0
0 to 300
INP1
⇒
DELAY
SEC
No.21
screen
"AL25
:
Contact input signal detection 1"
OFF detection timer
0
0 to 10
INP1
⇒
OVER
SEC
No.22
screen
Changing of "AL26
:
Contact input signal detection 2"
FLT
OFF/WRN/FLT
INP2
⇒
ALARM
-
No.23
screen
"AL26
:
Contact input signal detection 2"
reading delay timer
0
0 to 300
INP2
⇒
DELAY
SEC
No.24
screen
"AL26
:
Contact input signal detection 2"
OFF detection timer
0
0 to 10
INP2
⇒
OVER
SEC
No.25
screen
Changing of "AL29
:
Communication error alarm"
WRN
OFF/WRN/FLT
COMM
⇒
ALARM
-
No.26
screen
Detection time for "AL29
:
Communication error alarm"
30
1 to 600
COMM
⇒
TIME
SEC
No.27
screen
Only when the abnormality occurs Pump
operation possible time
0.0
0 to 9999
PUMP
⇒
TIME
SEC
No.28
screen
Only when the abnormality occurs Pump
only possible operation temperature
40.0
5.0 to 45.0
PUMP
⇒
TEMP
℃
No.29
screen
Switch maintenance notification
OFF
OFF/WRN/FLT
MANT
⇒
ALARM
-
No.30
screen
Changing of "AL17
:
Flow rate failure alarm"
3
FLT
OFF/WRN/FLT
LOW
⇒
FLOW
⇒
ALARM
-
5.5.4
ScreenNo.
Item
Display unit
Unit
display
Reference
page
Upper stage
(
White
)
Lower stage
(Green)