Chapter 5 Display and Setting of Various Functions
HRR Series
5.5 Advanced setting mode
5-39
Output of the circulating fluid temperature drop alarm.
15.
Press the [▼] key. Displays screen for output setting of the circulating fluid temperature
drop alarm.
Output of alarm AL15: Circulating fluid temperature drop
Set value
Contents
Initial value
ON
Contact output, or serial communication
signal is output.
○
OFF
Signal is not output.
―
Switching of the ambient temperature alarm
16.
Press the [▼] key. Displays screen for changing the chiller behaviour when the
ambient temperature alarm occurs.
Displayed for air-cooled type only. (This item is not displayed for water-cooled type)
Operation for alarm AL11: Ambient temperature alarm can be selected.
Set value
Contents
Initial value
OFF
Alarm is not generated
○
WRN
Operation of this product will continue when the
alarm occurs.
―
FLT
Operation of this product will stop when the alarm
occurs.
―
Ambient temperature upper limit alarm
17.
Press the [▼] key. Displays screen for setting the upper limit of the ambient
temperature. Displayed for air-cooled type only. (This item is not displayed for
water-cooled type)
Upper limit of alarm AL11: Ambient temperature alarm can be changed.
●
Setting range: 10.0 to 45.0
℃
(initial value: 40.0
℃
)
RUN
RUN
℃
RUN
Output of the circulating fluid temperature drop alarm.
AMB
⇒
H
I
TEMP
(
Alternately displayed
)
TEMP
⇒
OU
T
LO
⇒
OU
T
P
(Alternately displayed)
AMB
⇒
TEMP
⇒
ALARM
(
Alternately displayed
)
Ambient temperature upper limit alarm
Operation of the ambient temperature alarm