HRX-OM-X084
Chapter 5
Display and Setting of Various Functions
5.5 Advanced setting mode
HRR Series
5-44
Table 5.5-1 List of alarms which allow to continue pump operation
1 Select from OFF/ WRN/ FLT.
2
Select from WRN/ FLT.
3 Can be set only for air-cooled type.
4 Option DM (Electric conductivity control type, de-ionized water piping type) only. Alarm is
automatically released when the electric conductivity returns within the range.
5 Select from OFF/ WRN.
6 Not generated for options Z.
7 Not generated for options Z and Z1.
8 For option T1.
9 Only for water-cooled type.
Upper line
(White)
Lower line
(Green)
AL01
Low level in tank
FLT
AL01
LOW
⇒
LEVEL
⇒
FLT
-
AL02
Low level in tank
WRN
AL02
LOW
⇒
LEVEL
⇒
WRN
-
AL04
Water leakage
6
WRN
1
AL04
WATER
⇒
LEAK
○
AL05
Pump inverter error
*8
WRN
AL05
PUMP
⇒
INV
-
AL06
Internal fan stop
*9
WRN
AL06
FAN
⇒
ERROR
-
AL09
Circulating fluid discharge
pressure rise
FLT
2
AL09
HIGH
⇒
PRESS
-
AL10
Flow rate decreased
7
WRN
1
AL10
LOW
⇒
FLOW
⇒
WRN
○
AL11
Ambient temperature is
out of the range
3
OFF
1
AL11
AMB
⇒
TEMP
⇒
OUT
○
AL12
Electric conductivity
increase
4
WRN
5
AL12
DI
⇒
ERROR
-
AL13
NOT TEMP READY
OFF
1
AL13
TEMP
⇒
READY
⇒
ERROR
○
AL14
Circulating fluid
temperature increase
OFF
1
AL14
TEMP
⇒
OUT.HI
○
AL15
Circulating fluid
temperature decrease
OFF
1
AL15
TEMP
⇒
OUT.LO
○
AL17
Low flow rate
7
FLT
1
AL17
LOW
⇒
FLOW
⇒
FLT
-
AL18
High circulating fluid
discharge temp.
FLT
AL18
TEMP
⇒
FLT
-
AL19
High circulating fluid
return temp.
FLT
AL19
RET
⇒
TEMP
⇒
FLT
○
AL21
High circulating fluid
discharge pressure
FLT
AL21
HIGH
⇒
PRESS
⇒
FLT
-
AL22
Low circulating fluid
discharge pressure
FLT
AL22
LOW
⇒
PRESS
⇒
FLT
-
AL24
Memory error
FLT
AL24
MEM
⇒
ERROR
○
AL25
Contact input 1 signal
detection
FLT
1
AL25
INP1
⇒
ERROR
○
AL26
Contact input 2 signal
detection
FLT
1
AL26
INP2
⇒
ERROR
○
AL27
Forced stop
FLT
AL27
FORCE
⇒
STOP
-
AL28
Notice for maintenance
OFF
1
AL28
MANT
⇒
ALARM
○
AL29
Communication error
WRN
1
AL29
COMM
⇒
ERROR
○
AL30
Compressor circuit error
FLT
AL30
REF
⇒
ERROR
⇒
0000
○
AL31
Sensor error
FLT
AL31
SENS
⇒
ERROR
⇒
0000
-
AL32
Controller error
FLT
AL32
CTRL
⇒
ERROR
⇒
0000
-
Alarm
no.
Alarm name
Initial
value
Display
Alarms which allow to
continue pump operation