HRX-OM-X084
Chapter 3 Transport and Setting Up
3.2 Installation
HRR Series
3-2
3.2 Installation
3.2.1 Environment
The product must not be operated, installed, stored or transported in the following
conditions. Potential malfunction or damage to the product may occur if these
instructions are disregarded.
●
Location that is outside.
●
Location that is exposed to steam, salt water or oil.
●
Location that is exposed to dust or powder material.
●
Location that is exposed to corrosive gas, organic solvent, chemical solution,
or flammable gas. (The product is not explosion-proof.)
●
Location where the ambient temperature is out of the following range:
In transportation and In storage 0 to 50°C
(with no water or circulating fluid in piping)
During operation
5 to 40°C
●
Location where the ambient humidity is out of the following range or where
condensation occurs:
In transportation and storage 15 to 85%
In operation 30 to 70%
●
Location that is exposed to direct sunlight or heat radiation.
●
Location that is near heat sources and poor in ventilation.
●
Location that is subjected to abrupt changes in temperature.
●
Location that is subjected to strong electromagnetic noise (intense electric
field, intense magnetic field, or surges).
●
Location that is subjected to static electricity, or conditions where static
electricity can discharge to the product.
●
Location that is subjected to strong high frequencies raditation(microwaves).
●
Location that is subjected to potential lightning srtike
●
Location at altitude of 3000m or higher (except during product storage and
transport). Refer to below for details.
●
Location where the product is affected by strong vibrations or impacts.
●
Condition that applies external force or weight causing the product to be damaged.
Do not stack the product on top of each other.
●
Location without adequate space for maintenance as required
●
For the product installation or operation in accordance with UL standards, see below.
Do not set up the product in places possibly exposed to leakage of
flammable gas. Should any flammable gas stay around the product,
the product may cause a fire.
Do not use the product outdoors. If the product subjected to rain or
water splash it may cause electrical shock, fire or failure.
Keep the product upright on a rigid and flat floor which can resist the
weight of the product, and take measures to prevent the product from
tipping over. Improper installation may cause water leakage, tipping,
damage of the product or injure the operator.
Keep the ambient temperature of the product between 5 to 40
o
C.
Operation out of this ambient temperature range may cause a
malfunction of the product. Operating the product in an environment
temperature of 40
o
C may reduce the heat discharging efficiency of
the heat exchanger and the safety device may function, which stops
the product operation.
The installer/end user is responsible for carrying
out an acoustic noise risk assessment on the equipment after
installation and taking appropriate measures as required.
Summary of Contents for HRR010-A-10 Series
Page 14: ...HRX OM X084 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Page 46: ...HRX OM X084 Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRR Series 3 24...
Page 120: ...HRX OM X084 Chapter 6 Option 6 5 Option Z HRR Series 6 6...
Page 165: ......