HRX-OM-S010
Chapter 4 MODBUS communication function
HRS100/150 Series
4.10
Register Map
4-17
4.10 Register Map
Address
Bit Format
R/W
15 14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0000h
Circulating fluid discharge
temperature
-110.0 to 150.0
o
C = FBB4h to 5DCh
(
0.1
o
C /dig
)
R
-166.0 to 302.0
o
F = F984h to BCCh
(
0.1
o
F /dig
)
0001h
Circulating fluid flow rate
0.0 to 195.0L/min = 0h to 79Eh
(
0.1L/min/dig
)
0002h
Circulating fluid discharge
pressure
0.00 to 3.00MPa = 0h to 12Ch
(
0.01MPa/dig
)
0 to 435PSI = 0h to 1B3h
(
1PSI/dig
)
0003h
Circulating fluid electric
conductivity
2.0 to 48.0 microS/cm = 14h to 1E0
(
0.1microS/cm/dig
)
0004h
Status flag
0005h
Alarm flag 1
0006h
Alarm flag 2
0007h
Alarm flag 3
0008h
Alarm flag 4
0009h
Reserved
000Ah
Reserved
000Bh
Circulating
fluid
set
temperature
5.0 to 35.0
o
C = 32h to 15Eh
(
0.1
o
C /dig
)
R/W
41.0 to 95.0
o
F = 3B6h to 410h
(
0.1
o
F /dig
)
000Ch
Reserved
1
000Dh
Reserved
000Eh
Reserved
000Fh
Reserved
1
:
Commands to run
4.10.1 Circulating fluid discharge temperature
Read the circulating fluid discharge temperature in the selected temperature
unit (°C or °F). Read the circulating fluid discharge temperature which is
displayed on the operation display panel PV. (Offset temperature is
displayed if offset function is set).
4.10.2 Circulating fluid discharge pressure
Read the circulating fluid flow rate.
4.10.3 Circulating fluid discharge pressure
Read the circulating fluid discharge pressure in the selected pressure unit
(MPa or PSI).
4.10.4 Circulating fluid electric conductivity
Read the circulating fluid electric conductivity. In case of [SE.19 Electric
conductivity sensor setting] is off, value is 0 [microS/cm].