5.20 Alarm customizing function
5.20.1 Alarm customizing function
The operation and the threshold when alarm signal is output can be
customized. Customers should set them depending on the applications.
In the table 5.20-1, the contents of the alarm customizing are described.
①
Alarm operations (In the table 5.20-1, 2, 3, 4 Alarm initial setting and customizing)
A.STP
: Stops the pump, compressor and fan with the alarm
A.RUN
: Continues running the pump, compressor and fan
with the alarm
P.RUN
: Stops the compressor and fan, and continues
running the pump with the alarm *1
OFF
: Does not generate the alarm.
About the mark of each alarm
operation
○
:
Initial setting
●
:
Possible to select
-
:
Impossible to select
*1: The alarm operations of all the object alarms of the P.RUN cannot be customized individually but collectively.
②
Alarm thresholds and others
(In the table 5.20-1, 2, 3, 4 Alarm setting and customizing)
The alarm thresholds and other values can be changed from the initial values to new values within the settable
range. The parts of
–
mark cannot be changed.
Table 5.20-1 Alarm setting and customizing (1/4)
Code
Alarm name
①
Alarm operations
②
Alarm threshold and others
1
Display
A.S
T
P
A.RUN
P
.RUN
O
F
F
Display
Default
setting
Settable range
AL01
Low level in tank
● ○ -
-
-
-
AL02
High
circulating
fluid
discharge
temp
-
○ -
-
-
-
-
AL03
Circulating
fluid
discharge
temp.
rise
● ○ - ●
Temperature
45.0
o
C
(113.0
o
F)
(----)
2
5.0 to 55.0
o
C
(41.0 to 131.0
o
F)
Monitoring method
0
0 to 3
Monitoring start timer
---- (0)
3
0 to 600 minutes
Range over detection timer
5
5 to 999 seconds
1: Values in
゚
F are displayed when SE12 is F.
2: The default setting when AS03 is OFF.
3: The default setting when AS21 is 2 or 3.