Chapter 8 Control, Inspection and Cleaning
8.3
Consumables
HRSH Series
8-6
8.2.5
Inspection for winter season
Anti-freezing function
To prevent the circulating fluid freezing during winter, this function operates
pump automatically to heat the circulating fluid by the pump
’s heat radiation. If
there is a possibility of the circulating fluid freezing due to changes in the
installation and operating environment (season and weather), set this function in
advance.
*For details, refer to
”.
Warming up function
During winter or night, this function operates pump automatically to heat the
circulating fluid by the pump
’s heat radiation to keep the circulating fluid
temperature around the warming up function set temperature. If it is necessary to
shorten the circulating fluid temperature rising time, set this function in advance.
*For details, refer to
For freezing of the facility water
Please discharge the facility water from facility water circuit when there is fear of a
freeze.
*For the details, refer to
”.
8.3 Consumables
Replace the following parts depending on their condition.
Table 8-3 Consumables
Part number
Name
Qty.
Remarks
HRS-S0306
Dust-proof filter
1
1 pc. is used per unit
HRS-S0307
Mechanical seal set
1
1 set is used per unit
HRS-S0350
Mechanical seal set
1
1 set is used per unit (For option M)
The power supply should be ON for these functions. Otherwise these
functions cannot start.