5.20.2 Alarm customize function setting and checking
The table below explains the setting items of the alarm customize function
and the initial values.
Table 5.20-5
List of set alarm customizing function(1/2)
Display
Content
Object alarm
Change content
Default
setting
1
Code
Alarm name
Changing of low tank level
AL01
Low level in tank
Alarm operation
A.RUN
Changing of circulating
fluid
discharge
temperature rise
AL03
High circulating fluid
discharge temp
Alarm operation
A.RUN
Detection temperature for
circulating fluid discharge
temperature rise
Alarm threshold
45.0
o
C
(113.0
o
F)
(----)
Changing of circulating
fluid
discharge
temperature drop
AL04
Circulating
fluid
discharge temp. drop
Alarm operation
A.RUN
Detection temperature for
circulating fluid discharge
temperature drop
Alarm threshold
1.0
o
C
(33.8
o
F)
(----)
Changing of circulating
fluid discharge pressure
rise
AL08
Circulating
fluid
discharge temp. rise
Alarm operation
A.RUN
Detection pressure for
circulating fluid pressure
rise
Alarm threshold
0.55MPa
(80PSI)
Changing of circulating
fluid discharge pressure
drop
AL09
Circulating
fluid
discharge
pressure
drop
Alarm operation
A.RUN
Detection pressure for
circulating fluid discharge
pressure drop
Alarm threshold
0.05MPa
(7PSI)
(----)
Changing
of
communication error
AL19
Communication error
Alarm operation
OFF
Monitoring
time
of
communication error
Alarm threshold
----
(30)
Changing of contact input
1 signal detection
AL31
Contact input 1 signal
detection
Alarm operation
A.STP
Changing of contact input
2 signal detection
AL32
Contact input 2 signal
detection
Alarm threshold
A.STP
Changing of DC line fuse
cut
AL21
DC line fuse cut
Alarm operation
A.STP
Temperature
alarm
monitoring method
AL03
Circulating
fluid
discharge temp. rise
Selection
of
monitoring method
0
AL04
Circulating
fluid
discharge temp. drop
*1: Regarding the detail of the default setting, refer to
“Table 5.20-1 Alarm setting and customizing (1/4)
to (4/4)
”.